F03 DISPLAY OR SET BATTERY TEMPERATURE
If there is no external temp sensor and F-16 is OFF (factory default), this
function sets ambient battery temperature used to caluculate rate corrected
battery capacity which drives the LED bar graph and the Time remaining
display. Feature not available on units with serial numbers prior to 05000.
DEFAULT: 20C
RANGE: 0-40C
STEP: 1C
If F16 is ON and an optional external temperature sensor is connected
between Pin 6 and Pin 8 (ground), F03 will display temperature (0-99 C).
Temperature will continue to be displayed until one of the two front panel
buttons is pressed. Active Temperature display is annunciated by the
absence of front panel status indicators. If 0 is displayed at normal (~ 20
C) temperatures, an open temperature probe should be assumed. If >99 is
displayed at normal temperatures, a shorted probe should be suspected.
F04 TURN ON KWHRS DISPLAY
Kilowatt-hours are displayed in the Ah mode. (Note: The Kwhr display
does not take into account Charging Efficiency. As a condition for a
recalculation of the CEF and an automatic reset of Amp-hours to zero,
100% of the energy removed from the battery must be returned. The
number in the Kwhr display must be zero or positive to allow a
recalculation of the CEF and an automatic reset to zero. You may use this
function to verify that this condition has been met.)
DEFAULT: OFF
RANGE: OFF or ON
F05 USE ALTERNATIVE ENERGY (AE) DEFAULTS
Changes time to meet Charged Parameters to 1 minute from normal
5minutes. (Also consider changing Charged Current to 4%)
DEFAULT: OFF
RANGE: OFF or ON