14 - START-UP
Figure 14-9 - Taking combustion analysis
Figure 14-10 - Gas valve
D - Gas inlet tapping point.
E - CO2 regulation screw.
F - Factory regulation screw (do not touch).
020010.01.042
E
D
F
E
D
F
020010.01.022
14.8 - Check the CO2 content and
make any necessary adjustment
Table 14-8 shows the correct values of CO2 for a appliance
working in normal conditions, at an altitude of less than 1000
metres. A different value from the one shown can cause
malfunctions. A combustion analysis must be carried out to
check and make any necessary adjustment to this value.
Proceed as follows:
14.8.1 - Check the CO2 content and make
any necessary adjustment on appliance
models 34T, 60T and 70T
WARNING! If during this procedure a CO
value of more than 1000 ppm is detected, turn off the
appliance and contact the dealer.
1.- If one is not already present, you will have to make a hole
for the combustion analysis, located about 200 mm from the
exhaust gases outlet pipe (see figure 14-9 corresponding to
stopper “F”).
2.- Turn on the appliance and open the link between terminals
“10” and “11”;
3.- Make sure that the temperature demanded is higher than
that of the water heater;
4.- Go into the installer menu (see section 15.9 and set
parameter
2010
to
HIGH.
Now the appliance will operate
at maximum power for 20 minutes;
5.- Wait two or three minutes for the CO2 to stabilise;
6.- Insert the sensor to read the value of CO2 in point “F” shown
in figure 14-9;
7.- Compare the value of CO2 detected with that shown in table
14-8; make sure you read the value for the type of gas being
used. If the value of CO2 is not that shown in table 14-8, you
must correct it using screw “E” in figure 14-10. Using a 2.5
mm six-sided spanner (turn the screw clockwise to reduce
the value of CO2 and anticlockwise to increase it), make
small turns, always waiting for the CO2 value to stabilise
before continuing with further movements, until you reach
the desired value.
8.- Once you have reached the correct value of CO2 as in table
14-8, seal the screw with red paint or a similar system to
discourage any tampering with it.
9.- Set parameter
2010
at
LOu
The appliance will now
operate at minimum power for 20 minutes.
10.- Wait two or three minutes for the CO2 to stabilise;
11.- Compare the reading for the value of CO2 with that shown
in table 14-8, make sure you read the value for the type of
gas being used. The value of CO2 must fall within the values
shown, if that is not the case you must turn of the appliance
and contact the manufacturer.
12.- Set parameter
2010
to
OFF
to return the appliance to
normal operation.
13.- Close the combustion analysis hole in figure 14-9, with
a suitable stopper “F” as shown in the manufacturer’s
instructions for the outlet pipe.
WARNING! Once stopper “F” is in position with
the appliance at maximum power, check there are no
leaks of exhaust gases.
F - Taking combustion analysis
F
Содержание POOLDENS 100T
Страница 2: ......
Страница 79: ...79 POOLDENS COSMOGAS 16 MAINTENANCE Figure 16 14 Multi wire wiring diagram part 2 continued from previous page ...
Страница 82: ...82 POOLDENS COSMOGAS 16 MAINTENANCE Figure 16 15 Multi wire wiring diagram part 3 continued from previous page ...
Страница 95: ......
Страница 96: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...