39
POOLDENS
COSMOGAS
020014.01.029
C
E
F
020014.01.028
12 - INSTALLATION - Flue gas outlet duct
12.1.2 - Flue gas outlet system
The appliance is supplied as standard with the joint to
connect the flue gas outlet. For installation proceed as
shown in figure 12-2.
1.- insert pipe “E” into joint “C” taking care that the gasket
provided is in the correct position;
Polypropylene pipes, more resistant to the formation of
condensate, must be installed.
Take particular care when installing pipes in the part that
goes through the wall to the outside; normal maintenance
operations must always be possible, so install the pipes
in a sheath, in order to be able to take them out.
The horizontal sections must always have a slope of at
least 2% towards condensate outlet devices.
The appliance is already provided with a condensate
collector that must be connected to an outlet pipe (see
section 10).
WARNING! This condensate outlet is designed
to make all the liquid produced by a single appliance
drain out. If more than one appliance is installed, each
should be provided with its own condensate outlet.
The flue gas outlet system can be extended up to a
maximum distance as shown in section 17. Each 90° bend
has a loss equivalent to that reported in section 17.
WARNING! The flue gas outlet terminal must be
correctly protected against the effects of the wind.
WARNING! Fix the joints between the various
components of the outlet pipe mechanically using
fastening or other systems. See figure 12-4.
WARNING! The temperature of the outlet pipe
during operation can reach 90°C. If it goes through
walls that are sensitive to these temperatures, use a
heat-insulating protective sheath.
WARNING: The outlet duct must be suitably
supported by rigid rods positioned not more than 1 m
from each other. The rods must be fastened to rigid
walls that can take the weight of the duct itself.
Figure 12-4 - Fastening of flue gas outlet pipe
Figure 12-2 - Installation of flue gas outlet system
Figure 12-3 - Assembled system
Air
Inlet
Flue gas
outlet
Air
Inlet
Flue gas
outlet
Содержание POOLDENS 100T
Страница 2: ......
Страница 79: ...79 POOLDENS COSMOGAS 16 MAINTENANCE Figure 16 14 Multi wire wiring diagram part 2 continued from previous page ...
Страница 82: ...82 POOLDENS COSMOGAS 16 MAINTENANCE Figure 16 15 Multi wire wiring diagram part 3 continued from previous page ...
Страница 95: ......
Страница 96: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...