51
POOLDENS
COSMOGAS
14.4 - Conversion of appliance models
34T, 60T and 70T from one type of gas
to another
WARNING! Read these instructions carefully
before making the gas change:
- The installation, calibration or modification of the gas
appliance must be carried out by specialised people,
in compliance with the law;
- Check and make sure that the type of gas the appliance
is supplied with is compatible with the adjustment kit
in your possession;
- Do not supply the appliance with a type of gas other
than those anticipated.
Figure 14-4 - Replacing gas nozzle
Figure 14-3 - Raising gas valve
Figure 14-2 - Dismantling gas valve
A
H
M
020010.01.020
L C
B
020010.01.021
G
020010.01.019
Contents:
The kit (supplied as standard with the appliance) is made up of
- label certifying the new type of gas, a gas nozzle for each
burner and an instruction sheet;
To carry out the change of gas, proceed as follows:
1 - Turn off the appliance by moving the main switch to OFF
(detail “T” in figure 15-1);
2 - Turn off the gas supply cock;
3 - open the appliance casing as described in section 16.2;
4 - Undo junction “H” in figure 14-2;
5 - With the aid of a screwdriver, remove fork “A” in figure 14-2;
6 - Remove the gas valve with junction “C” as in figure 14-3
(paying attention to the OR “L” in figure 14-3);
7 - Replace nozzle “G” in figure 14-4 with the one in the kit,
checking it corresponds in diameter to that shown in table 14-8;
8 - Replace the gas valve paying attention to the correct
position of the OR “L” in figure 14-3 and to the joint gasket
“H” in figure 14-2;
9 - Replace fork “A” in the locking housing;
10 - Tighten joint “H” in figure 14-2;
11 - Open the gas supply valve;
12 - Check that there are no leaks from joint “H” in figure 14-2;
WARNING!
Carry out the gas seal test only with
a soap water solution. The use of naked flames is
absolutely forbidden.
13 - Turn on the appliance by moving the main switch to ON
(detail “T” in figure 15-1);
14 - Completely undo screw “E” in figure 14-6 in an
anticlockwise direction;
15 - Check gas pressure by following section 14.7, the minimum
pressure must not be less than 10 mbar while the maximum
must not exceed 45 mbar;
16 - Check and adjust the CO2 following the procedure in
section 14.8 and checking the value in figure 14-8;
WARNING!
The measurements taken must be
done with guaranteed calibrated instruments that
ensure an accurate reading.
17.- Check the appliance’s power by following section 14.9;
18.- apply the adhesive data plate
(see figure 14-7) to the
right-hand side of the appliance, in place of the label that
identified the old control status, to certify the appliance’s
new control status, in the following way: apply label “B” if
the appliance has been converted from methane to LPG;
apply label “A” if the appliance has been converted from
LPG to methane.
WARNING!
If there is a smell of gas:
A - Do not turn on any electrical device, including a
telephone, or any item that could cause sparks;
B - Immediately open doors and windows to create
a draught that will quickly clear the room of gas;
C - From another room, or failing that from a
neighbour’s, immediately call a professionally
qualified technician or the gas supply company.
In their absence, call the fire service.
14 - START-UP
020022.01.008
NO
YES
Содержание POOLDENS 100T
Страница 2: ......
Страница 79: ...79 POOLDENS COSMOGAS 16 MAINTENANCE Figure 16 14 Multi wire wiring diagram part 2 continued from previous page ...
Страница 82: ...82 POOLDENS COSMOGAS 16 MAINTENANCE Figure 16 15 Multi wire wiring diagram part 3 continued from previous page ...
Страница 95: ......
Страница 96: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...