8.15 - Checking the ionisation current
In any operating status, also during verifications of minimum
and maximum power stated in chapter 8.14, the ionisation
current value can be consulted on parameter
1008
present
in the “User menu” (chapter 7.17). This value must be between
1.5 and 3 uA (microampere) at minimum power and between
5 and 8 uA at maximum power.
8.16 - Checking combustion
performance
On the basis of national laws regarding gas appliances, the
combustion performance must be checked periodically;
To do this, operate exactly as stated in chapter 6.8 and also
check, in addition to CO2, the combustion efficiency, which
must be over 96%.
Figure 8.12 - Water sensors curve
Figure 8.13 - External temperature sensor curve
8 - MAINTENANCE
8.17 - Water temperature
measurement sensors
The temperature sensors are positioned on the boiler’s
exchanger body. The electric resistance existing between
the two contacts of the sensor, must correspond with that
stated in figure 8.12.
The temperature sensors are:
1001
,
1002
,
1005
,
1006
,
1007
and
1014
, the positioning of which can
be verified in figure 3.1.
8.18 - External temperature sensor
On request, the external temperature sensor can be
connected to the boiler
1004
(see chapter 5.14.4). The
electric resistance existing between the two contacts of the
sensor, must correspond with that stated in figure 8.13.