8.12 - Emptying the appliance
Proceed as follows to empty the appliance:
1.- generate a central heating request;
2.- set the central heating temperature at the lowest value
possible, with the purpose of cooling the water inside the
boiler;
3.- switch the boiler off;
4.- close the plant load cock envisioned by the installer;
5.- connect a flexible hose to the drain cocks envisioned by
the installer and convey it onto the drain of a washbasin
or similar;
6.- open the drain cocks envisioned by the installer;
7.- open the central heating elements bleed valves. Start
from the highest central heating elements and continue
with the lowest
8.- once all of the water has been evacuated, close all of
the heating element vent valves and the drain cocks
envisioned by the installer.
ATTENTION !!! It is prohibited to recover and/
or re-use the water evacuated from the central heating
circuit for any purpose; this could be polluted.
8.13 - Fan
Switch-on of the fan only can be generated, accessing the
parameter
2010
situated inside the “Installer menu” (see
chapter 7.18) and set it on
FAn.
To go back to normal
operating conditions, set parameter
2010
again to
0FF.
8.14 - Minimum and maximum power
Appliance operation can be forced to its own minimum,
maximum, adjusted or ignition power. Proceed as follows:
1.- make sure that any cocks and thermostatic valves
downstream from the central heating circuit are open;
ATTENTION !!! During forcing of the delivery
temperature, it automatically goes to 93°C to give the
possibility to dispose of as much of the heat generated
by the boiler as possible. Check that the central
heating plant can support this temperature.
2.- access parameter
2010
found in the “installer menu”
(see chapter 7.18);
3.- set the parameter
2010
at the following value:
a)
LOu
to force the boiler to minimum power;
b)
Ign
to force the boiler to ignition power;
c)
HIgH
to force the boiler to maximum power;
d)
rEg
to force the boiler to the maximum central heating
power, as adjusted (Range Rated) in chapter 6.9,
parameter
2002
.
4.- To end forcing, take the parameter
2010
to the
0FF
value and press the RESET key.
ATTENTION !!! If during forcing, the power
supplied by the boiler is much higher than the
power absorbed by the plant, the boiler switches off
continuously to reach the maximum temperature
allowed (93°C).
8 - MAINTENANCE
Содержание MYDENS 60
Страница 63: ...63 MYDENS 60 COSMOGAS 8 MAINTENANCE ...
Страница 71: ......
Страница 72: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...