![COSMOGAS MYDENS 60 Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/cosmogas/mydens-60/mydens-60_installation-use-and-maintenance-manual_2670681031.webp)
31
MYDENS 60
COSMOGAS
6.1 - Operating
Before starting the appliance up, it si necessary to carry out
the following.
6.1.1 - User instructions
Instruct the user regarding correct use of the appliance and
the plant in general. In particular:
Give the installation and use manual and all
documentation contained in the packaging to the user.
Instruct the user concerning the special measures for the
exhaust of burned gases, informing them that they must
not be modified.
Inform the user regarding the control of the pressure
of the water required in the plant and the measures
necessary to fill and bleed the air.
Inform the user regarding the correct adjustment of
the temperatures, control units/room thermostats and
radiators for energy saving.
6.1.2 - Filling the condensate drain siphon
The siphon found inside the boiler (see figure 3.1 detail “33”),
must be filled with water to create the water head able to
prevent the fumes escaping from pipe “F” in figure 5.4.
Proceed as follows to do this: (refer to figure 6.1)
1.- loosen and remove the cap “R”;
2.- introduce a rubber hose into the opening “S” and the
other end of the hose into the funnel;
3.- use the funnel to slowly pour about 200 cm3 (a glass) of
water;
4.- re-mount everything in reverse order.
6 - OPERATING
Figure 6.1 - Filling the condensate drain siphon
ATTENTION !!! If the boiler remains off for
more than 3 months, the siphon must be filled again as
explained above.
6.1.3 - Filling the central heating plant
If the wording
FILL
, appears on the visual display when
the boiler is powered electrically, it means that the central
heating plant must be filled. Proceed as follows:
only use clean water from the main supply.
ATTENTION !!! The addition of chemical
substances such as anti-freeze must be performed in
compliance with the product instructions. In all cases,
these substances must not be introduced directly
inside the boiler.
1.- open the filling device envisioned by the installer
upstream from the appliance and fill the bar to about 1.5
bar (
FILL
will appear on the visual display);
2.- make sure there are no water leaks from the fittings;
3.- close the filling device envisioned by the installer
upstream from the appliance;
4.- bleed the heating elements;
5.- check the pressure on the boiler display again. If it has
dropped, load up to 1.5 bar again.
S
R
S
R
020005.01.006
Содержание MYDENS 60
Страница 63: ...63 MYDENS 60 COSMOGAS 8 MAINTENANCE ...
Страница 71: ......
Страница 72: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...