![COSMOGAS MYDENS 60 Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/cosmogas/mydens-60/mydens-60_installation-use-and-maintenance-manual_2670681046.webp)
46
MYDENS 60
COSMOGAS
7 - USE
2014
Icons test on the display. By pressing the RESET key, all of the
icons on the display light up. By pressing the RESET key again
to display goes back to normal operation
/
/
/
2020
Climatic adjustment: external temperature for central heating
switch-off
°C
From 0 to 35
22
2021
Climatic adjustment: project external temperature (winter)
°C
From -20 to 5
-5
2022
Climatic adjustment: flow temperature corresponding to the
project external temperature (winter)
°C
From 0 to 80
80
2023
Climatic adjustment: external spring-like temperature
°C
From 0 to 30
20
2024
Climatic adjustment: flow temperature corresponding to the
external spring-like temperature
°C
From 0 to 40
40
2027
Temperature reduction by room thermostat opening
°C
From 1 to 50
10
2040
Climatic adjustment: central heating boost temperature
°C
From 0 to 20
0
2041
Climatic adjustment: central heating boost time
min
From 0 to 30
20
2042
Protection against frequent switch-on in central heating mode:
time
sec
From 10 to 900
180
2043
Protection against frequent switch-on in central heating mode:
temperature differential
°C
From 0 to 20
16
2060
Domestic hot water minimum power level
%
From 1 to 50
1
2061
Domestic hot water maximum power level
%
From 1 to 100
100
2062
Post-circulation in domestic hot water mode
sec
From 10 to 900
120
2063
Maximum time for charging Indirect Water Heater
min
From 0 to 60
60
/
2064
Number of flow meter revs. for every litre of water
rpm/lt From 0 to 5
3,2
2066
Delay in the detection of the instantaneous domestic hot water sec
From 1 to 10
3
2067
Indirect Water Heater charging procedure
/
0 = the Indirect Water Heater
charging for the time set in the
parameter 2063;
1 = OFF, the domestic hot water
does not have priority over
heating;
2 = ON, the domestic hot water
always has priority over heating;
2
2080
Periodic maintenance meter
(after RESET, the meter automatically goes back to ON)
/
ON = Periodic maintenance
meter active;
OFF = Periodic maintenance
meter off;
RESE = Meter reset
OFF
2081
Periodic maintenance meter: maintenance request time
days
From 0 to 1000
1000
2100
Energy saving display
min
OFF = display always on
From 1 to 30 = delay to switch-
off in minutes.
5