Applications manual
For AME series
6.10.6
READ_RATED_IOUT [1Eh] [09h] [11h] [01h]
Return value : 1200
=>
12A
Return value : 250
=>
2.5A
If the front-end module is target, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
6.10.7
READ_VIN_POINT [1Eh] [09h] [12h] [00h]
6.10.8
READ_VOUT_POINT [1Eh] [09h] [12h] [01h]
6.10.9
READ_IOUT_POINT [1Eh] [09h] [12h] [02h]
If the instruction is executed on an output module other than the supported output modules, an
error is returned.(Error code 6 : Command that do not correspond to the setting target)
This command returns the rated current of the selected model.
The rated output current is set to the value of "Returned value / 100".
Examples of return value
This command returns the number of the decimal places of "MON_IOUT" command for the
position of decimal point.
Return value
2
This command returns the number of the decimal places of "MON_VIN" command for the
position of decimal point.
Return value
2
This command returns the number of the decimal places of "MON_VOUT" command for the
position of decimal point.
Return value
3
49
ver1.1E 2020.2.12