6.5 Commands to set output voltage sequence
6.5.1
SET_TON_DELAY_SLOT [0Fh] [
Argument
]
0 - 3000
Argument:900 => 900 msec
Argument value
No delay time is set for the RC terminal of each output module.
If the front-end module is target, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
6.5.2
READ_TON_DELAY_SLOT_PRM [1Eh] [09h] [1Dh] [06h]
If the front-end module is target, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
6.5.3
SET_TON_DELAY_FACTORY_SETTING [1Eh] [09h] [0Dh] [00h]
0
The setting by this command causes a delay due to the processing time of the slave which is the AME
series.
This is enabled at AC input with power conversion ready, but the internal delay of up to 800ms
occurs.
The factory default is "0".
This command sets the value of the delay time, in ms, from when power conversion is
ready to when it starts. (See Figure 6.5.1.)
*The power conversion starts after delay time set by
"SET_TON_DELAY_SLOT" command when conditions such as AC input,
disabling the GI and enabling the Remote ON are met.
This command restores the delay time to power-on set by "SET_TON_DELAY_SLOT" command for
all slots to the factory default.
Return value
Figure 6.5.1 Timing diagram of "SET_TON_DELAY_SLOT"
Settable range
Example of argument
Return value
This command returns the value (the argument value) set by
"SET_TON_DELAY_SLOT" command.
The delay time to power-on that has been stored in the non-volatile memory by
"SYS_STORE_USER_SETTING" command does not change.
Applications manual
For AME series
SET_TON_DELAY_SLOT
Vin
GI
Com. remote on/off
Vout
output ON
output OFF
output ON
output OFF
26
ver1.1E 2020.2.12