Applications manual
For AME series
6.6.15
SET_VOUT_HV_ALARM [16h] [1Ch] [Argument]
Rated voltage x 25% - Rated voltage x 200% (maximum 65.5V)
argument:520 => 52.0V
argument value
If the front-end module is target, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
6.6.16
READ_VOUT_HV_ALARM_PRM [1Eh] [09h] [1Bh] [1Fh]
If the front-end module is target, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
6.6.17
SET_VOUT_ALARM_FACTORY_SETTING
[1Eh] [09h] [0Bh] [1Dh]
If the front-end module is target, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
This command returns the value (argument value) set by "SET_VOUT_HV_ALARM"
command.
If the instruction is executed on an output module other than the corresponding output modules, an
error is returned.(Error code 6 : Command that do not correspond to the setting target)
This command sets the threshold voltage for the alarm signal from LV terminal at when
the output voltage rises.
It sets the value of "Argument / 10" to the output threshold voltage, in V, for the alarm signal from the
LV terminal.
With this command, it can not be set to lower value than the calculation below.
Calculation: Value set by "SET_VOUT_LV_ALARM" c 20% of Rated voltage
This command sets the value set by "SET_VOUT_LV_ALARM" command and
"SET_VOUT_HV_ALARM" command to the factory default.
Return value
If the instruction is executed on an output module other than the corresponding output modules, an
error is returned.(Error code 6 : Command that do not correspond to the setting target)
If the instruction is executed on an output module other than the corresponding output modules, an
error is returned.(Error code 6 : Command that do not correspond to the setting target)
Return value
0
Settable range
Example of argument
35