34
EN
W415-1398 / C / 06.15.17
NOTE : Fastening hardware provided with appropriate roof terminal and liner kits.
A.
Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case
the venting is to be adequately supported using either an alternate method suitable to the
authority having jurisdiction or the optional roof support.
B.
Stretch
the inner fl ex pipe to the required length. Slip the inner fl ex pipe a minimum of 2”
(51mm) over the inner pipe of the air terminal connector and secure with a minimum of 3
screws. Seal using a heavy bead of Mill Pac sealant (W573-0007) (not supplied).
C.
Repeat using the outer fl ex pipe, using a heavy bead of red RTV silicone (W573-0002) (not
supplied) and a minimum of
3 screws.
ROOF SUPPORT
D.
Thread the air terminal connector / vent pipe assembly down through the roof. The air
terminal must be positioned vertically
INNER PIPE
and plumb. Attach the air terminal
connector to the roof support, ensuring that the top of the air terminal is 16” (40.6cm) above the
highest point that it penetrates the roof.
AIR
E.
Remove nails from the shingles, above and to the sides of the air
TERMINAL
terminal connector. Place the fl ashing over the air terminal connector
CONNECTOR
leaving a min. 3/4” (19mm) of the air terminal connector showing
MILL PAC
above the top of the fl
ashing. Slide the fl ashing underneath the
SEALANT
sides and upper edge of the shingles. Ensure that the air terminal
(W572-0007)
connector is
properly centered within the fl ashing, giving a 3/4”
(19mm) margin all around. Fasten to the roof. Do not nail through
INNER FLEX PIPE
the lower
portion of the fl ashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and top edges of the
OUTER FLEX PIPE
fl ashing
with roofi ng material.
F.
Aligning the seams of the terminal and air terminal connector, place the terminal over the air
terminal connector making sure the vent pipe goes into the hole in the terminal. Secure with 3
screws.
2” (51mm)
AIR INLETBASE
G.
Apply a heavy bead of weatherproof caulking 2” (51mm)
CAULKING
above the fl ashing. Install the storm collar around the air
terminal and slide down to the caulking. Tighten to ensure that
STORM COLLAR
a weather-
tight seal between the air terminal and the collar is
WEATHER
achieved.
SEALANT
H.
If more vent pipe needs to be used to reach the appliance see “HORIZONTAL AIR TERMINAL
INSTALLATION” section.
24.1D
FLASHING
4.2.3 APPLIANCE VENT CONNECTION
A.
Install the inner exhaust fl ue collar to the appliance. Secure
#8 X 1/2”
with a minimum
of 3 #8 screws. Seal the joint and screw
SELF
holes using Mill Pac sealant (W573-0007)
(not supplied).
DRILLING
B.
Install the outer fl ex pipe to the appliance. Attach and seal
SCREWS
2”
(50.8mm)
the joints using a red RTV silicone and a minimum of 3 #8
OVERLAP
screws.
Содержание CB30NTR
Страница 11: ...11 EN W415 1398 C 06 15 17 3 2 TYPICAL VENT INSTALLATION...
Страница 12: ...12 EN W415 1398 C 06 15 17 See VENTING section...
Страница 42: ...42 EN W415 1398 C 06 15 17 5 1 MINIMUM FRAMING DIMENSIONS...
Страница 46: ...46 EN W415 1398 C 06 15 17 MAXIMUM REAR VENT CLEARANCES EXAMPLE 1...
Страница 55: ...55 EN W415 1398 C 06 15 17 D ein stall the pre vio usly rem ove d sec urin g scr ews SIDE VIEW X5...
Страница 83: ......
Страница 84: ......