80
Fault Isolation
2582954_D_EN_1811_Nortec-EL_OM
Nortec EL
Code
Message
Probable Cause
Corrective Action(s)
Warning
Fault
W23
E23
Current T/O (timeout)
No heating current to electrodes.
Failure of one or more phases of the
heating current.
– Check the power supply. Check
the optional primary fuse (if
installed).
– Check/replace the main contac
-
tor, if necessary.
Water supply line clogged, shutoff
valve closed, or a clogged filter.
Water pressure too low.
– Check the supply line, shutoff
valve, filter and water pressure.
Clogged or defective fill valve.
.
Replace the fill valve,
Excessive backpressure in the steam
line (duct pressure too high, steam
line too long or kinked), causing
water loss through the fill cup.
– Check duct pressure, inspect
steam installation. If necessary,
install the optional fill cup exten
-
sion kit.
Leaks in the water supply.
– Fix all water leaks.
W24
E24
Over Curr
Current draw in relation to the humidification demand is too high.
Humidity demand decreased too fast.
– The system regulates current
levels automatically to match the
humidity demand.
Clogged drain valve.
– Check/
.
Excessive scale build-up in the steam
cylinder.
– Replace the steam cylinder, if
necessary. Refer to
and Installation of Steam Cylinder" on
Water conductivity too high for the
type of steam cylinder installed in
the unit.
– Contact your local Condair
representative.
W25
E25
Excess Curr
Maximum permissible current draw exceeded.
Clogged drain valve.
– Check/
.
Excessive scale build-up in the steam
cylinder.
– Replace the steam cylinder, if
necessary. Refer to
and Installation of Steam Cylinder" on
Water conductivity too high for the
type of steam cylinder installed in
the unit.
– Contact your local Condair
representative.
–
E26
Current Off
Current is detected when the controller has not energized the contactor.
Contactor jammed or short-circuited.
– Check the secondary side of
contactor. Replace the contactor,
if necessary.
Current sensor on the driver board
not seated properly, or defective.
– Check the current sensor is
seated properly on the driver
board.
– Replace the current sensor, if
necessary.
Содержание Nortec EL-Series
Страница 56: ...56 Operator Interface 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 93: ...Notes...
Страница 94: ......