37
Operator Interface
Nortec EL
2582954_D_EN_1811_Nortec-EL_OM
Setpoint Tab, continued...
–
Setpoint Channel 1:
allows you to set the humidifier to
operate at a fixed humidity setpoint value at the specified
time and date.
Setting range:
0-95% RH
Factory setting:
40% RH
PI Control Parameters Tab, continued from previous page...
–
Band Channel 1:
allows you to set the proportional range
for the internal P/PI controller as a percentage of relative
humidity (% RH) within which the humidifier will modulate
between 0 and 100% output.
Setting range:
6-65%
Factory setting:
15%
–
ITime Channel 1:
allows you to set the integral time for
error corrections by the internal P/PI controller.
Setting range:
1-60 minutes
Factory setting:
5 minutes
–
Setpoint Channel 2:
allows you to set the high limit
setpoint value.
Note:
Setting range:
0-95% RH
Factory setting:
80% RH
–
Band Channel 2:
allows you to set the proportional range
for the internal P/PI controller as a percentage of relative
humidity (% RH) within which the humidifier will modulate
between 0 and 100% output.
Note:
This setting appears
only if
Setting range:
6-65%
Factory setting:
15%
–
Damp Channel 2:
allows you to set the time duration after
which the high limit setpoint value takes control of the
demand signal.
Note:
Setting range:
1-60 seconds
Factory setting:
5 seconds
Содержание Nortec EL-Series
Страница 56: ...56 Operator Interface 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 93: ...Notes...
Страница 94: ......