35
Operator Interface
Nortec EL
2582954_D_EN_1811_Nortec-EL_OM
Basic Tab, continued...
–
Control Channels:
allows you set whether the humidifier
is controlled by one or two signals.
Options:
Single
– single control.
Dual
– Two control signals (typically
a control, plus a high limit signal).
Factory setting:
Dual
–
Signal Type Channel 1/3:
allows you to select the signal
type of the incoming control signal.
Note:
This setting is
ignored if signal
is not set to "Analog". Channel 3
applies only to units with dual steam cylinders set to oper
-
ate in independent mode.
Options:
0-5V, 1-5V, 0-10V, 2-10V, 0-20V,
0-16V, 3.2-16V, 0-20mA, 4-20mA
Factory setting:
0-20V
–
Signal Type Channel 2/4:
allows you to select the signal
type of the incoming high limit signal.
Note:
This setting
is ignored if signal
is not set to "Analog". Channel 4
applies only to units with dual steam cylinders set to oper
-
ate in independent mode.
Options:
0-5V, 1-5V, 0-10V, 2-10V, 0-20V,
0-16V, 3.2-16V, 0-20mA, 4-20mA
Factory setting:
0-20V