Control Settings Menu
Each tab under the Control Settings menu is discussed below. Refer to the structure of the tabs in
Basic Tab
–
Source:
allows you to select the source of incoming con
-
trol/humidity signal to the humidifier.
Options:
Analog
– the control/humidity signals
are from analog sensors or humidis
-
tats connected to the humidifier's low
voltage terminal block.
Modbus
– the control signals are
from the BMS via the Modbus com
-
munication protocol.
BACnet/IP
– the control signals are
from the BMS via the BACnet/IP
communication protocol.
BACnet/MSTP
– the control signals
are from the BMS via the BACnet/
MSTP communication protocol.
LonWorks
– the control signals are
from the BMS via the LonWorks
communication protocol.
Factory setting:
Analog
–
Dual Cylinder Mode:
allows you to configure the opera
-
tion of humidifiers with dual steam cylinders.
Note:
This
function appears only on units with dual steam cylinders.
Options:
Parallel
– the cylinders operate in
parallel based on humidifier demand.
This results in a lower turn-down
ratio, but even wear on both steam
cylinders.
Series
– the cylinders are modu
-
lated in sequence to meet humidifier
demand. Cylinder A will operate from
0-50% demand, and Cylinder B will
operate from 51-100% demand.
Independent
– the steam cylinders
work independently based on control
signals from two separate zones.
Factory setting:
Series
Содержание Nortec EL-Series
Страница 56: ...56 Operator Interface 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 93: ...Notes...
Страница 94: ......