31
Operator Interface
Nortec EL
2582954_D_EN_1811_Nortec-EL_OM
Operation Tab, continued...
–
Overcurrent:
CAUTION!
Do not adjust this value unless instructed to
do so by a Condair representative.
Setting range:
0.0-2.0
Factory setting:
1.5
–
Low Conductivity:
allows you to adjusts the end-of-
cylinder-life detection to prevent false end-of-cylinder-life
detection when conductivity of the supply water is less
than 250 μS/cm.
Options:
On
– use when conductivity of the
supply water is less than 250 μS/cm.
Off – use when conductivity of the
supply water is greater than 250 μS/
cm.
Factory setting:
Off
–
Short Cycle:
allows you to enable or disable the function
that enforces a time delay between the humidifier stopping
and restarting steam production (to reduce mechanical
wear on contactors and other peripheral devices). This
function is typically used with On/Off controllers. It can also
be useful if a high limit humidistat is cycling the humidifier
on/off too frequently.
Options:
On
– the humidifier runs in short
cycle mode.
Off – the humidifier cycles normally.
Factory setting:
Off
Содержание Nortec EL-Series
Страница 56: ...56 Operator Interface 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 93: ...Notes...
Страница 94: ......