Cleaning
6.4.1 Cleaning Agents
Use only the cleaning agents described in the procedures below. Disinfectants may only be used if they
do not leave behind toxic residue. Rinse all parts thoroughly with clean tap water after cleaning.
Follow all instructions, and observe the safety precautions stated below.
CAUTION!
Risk of damage to the humidifier components!
Do not
use solvents, aromatized or halogenized hydrocarbons, or other harsh chemicals for
cleaning.
6.4.2 Cleaning Procedures
Water Hoses
Use a rubber mallet to knock out any scale buildup in the
hoses. Rinse the hoses thoroughly with hot tap water.
Fill valve
1
1 Strainer
Use a soft-bristled brush (not wire brush) to carefully remove
any scale buildup inside the fill valve and in the strainer.
Drain Valve - Valve Body
Use a soft-bristled brush (not wire brush) to remove any scale
buildup inside the valve body of the drain valve.