38
Operator Interface
2582954_D_EN_1811_Nortec-EL_OM
Nortec EL
RH Alerts Tab
Note:
This tab appears only if
is set to "RH P" or "RH PI".
–
RH Alerts:
allows you to enable or disable the alert func
-
tion that warns if sensed humidity is too high or too low.
Options:
On
– enables the function.
Off
– disables the function.
Factory setting:
Off
Note:
The following four settings are only available if the
RH Alerts function is enabled.
–
RH High:
allows you to set the upper limit value of the
humidity sensor signal. The RH High warning message
is triggered when the signal value exceeds this limit.
Setting range:
20-95%
Factory setting:
75%
–
RH Low:
allows you to set the lower limit value of the
humidity sensor signal. The RH Low warning message
is triggered when the signal value drops below this
limit.
Setting range:
20-95%
Factory setting:
20%
–
Sensor Min:
allows you to set the minimum signal
value of the humidity sensor. If the signal value drops
below this setting, the sensor is assumed to be dam
-
aged or disconnected. The RH Signal warning mes
-
sage is triggered when the signal value drops below
this limit, and humidification stops.
Setting range:
1-10%
Factory setting:
5%
–
Enable Input:
allows you to enable or disable steam
production using an external contact. When set to On,
steam production will not be allowed unless the points
of terminal X11 on the driver board are closed.
Options:
On
– enables the function.
Off
– disables the function.
Factory setting:
On
Содержание Nortec EL-Series
Страница 56: ...56 Operator Interface 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Страница 93: ...Notes...
Страница 94: ......