CDD 5.0: user manual – Rev.01
Page 47/63
5.8.3
Door Stopping space
This parameter permits to modify the stopping and reversing space after:
-
Deactivation of the commands
-
Reversing in progress due to commands switch of reversing source activation.
It is accessible only by external handset device: “Main Menu”
“Advanced Settings”
“Parameters”
“Reversing space”. The set value defines the space necessary to stop the door (measured on the belt). This
means that for center doors this space will be seen doubled on the panels. This parameter is accessible only
by external handset device.
Parameter
Range
Default value
Reversing space
[5 ; 60 ] mm
30mm
5.8.4
PC24:
“smooth” reopening
This parameter allows to enable/disable the reopening movements with a “soft” speed profile, especially
for heavy application, or when the elasticity of the system is very high.
Parameter value
Note
00 = Reopening with “soft”
profile NOT ACTIVE
(default value)
The controller applies, for the reopening or partial opening profiles, the standard
calculated speed profile
01 = Reopening with “soft”
profile ACTIVE
The controller applies, for the reopening or partial opening profiles, a reduced speed
profile respect to the calculated one
5.8.5
PC36: door opening maximum power option
This parameter permits to enable the maximum available power for the opening movement, in case of
particular heavy applications. The activation of this option allows to reach better performances, but has
negative effects on the motor lifetime, and mechanical system stability.
NOTE: it is strongly suggested to contact Computec technical support before setting this function, to better
evaluate other set-up opportunity.
Parameter value
Note
00 = Maximum opening
power NOT ACTIVE
(default value)
The controller applies, for the opening profiles, the factory pre-stores maximum
power
01 = Maximum opening
power ACTIVE
The controller applies, for the opening profiles, the maximum available power