Computec
CDD5.0
EN
CDD 5.0: user manual – Rev.01
Page 33/63
5.1.2
PC90: installed motor type
This parameter permits to set the installed motor type, applying the automatic selection or setting
manually the installed motor code, as reported in the table below:
Motor type
Reference image
00 = self-recognized
The door drive automatically detects the motor type connected at every
power on. To avoid the self-recognizing cycle at every power on, set
manually the motor type.
Motors automatically recognized:
01
02
12
13
01 = Moog 1Nm (4:1 belt) + Enc500
02 = Moog 2Nm (4:1 belt) + Enc500
12 = GR 63x25 + SG80K (15:1) + Enc100
13 = GR 63x55 + SG120 (15:1) +Enc100
20 = SN40 (15:1) + Enc100
-
21 = SN31 (15:1) + Enc100
-
23 = SN 22,6 (7:1) + Enc100
-
- Table 25: selectable motor list -
5.1.3
PC22: closing rotation sense
The motors installed on the field can have the rotation pulley mounted on the right or on the left respect to
the motor shaft: this means that the motor, to rotate in the correct sense need to rotate in opposite sense
based on the installation type. This parameter permits to configure the correct closing rotation sense, as
reported in the following table:
Parameter value
Notes
00 = clockwise
(default value)
The motor pulley, in frontal view, rotates in
clockwise
sense when door is closing.
01 = counter-clockwise
The motor pulley, in frontal view, rotates in
counter-clockwise
sense when door is
closing.
The check of the rotation sense can be executed with door operator switched off, or checking the door
movement with the door drive in Inspection mode.