Detector check in
Normal mode
Execute this step only if external optical detector, light
curtains or photocell are directly connected to the CDD
5.0, to the RVC input or to the X9 plug.
Activate the normal mode of the door drive, from the
Inspection mode, by pressing key
and check the
NORMAL led is ON.
During the door closing, interrupt the light curtains and
check the immediate reopening of the door, until the
door is completely open.
Remove any obstacle from the detector activation zone,
and check the door closing until the door is completely
closed.
Display visualization:
NORMAL led
ON
“CL” blinking
“IM” blinking.
“IM” fixed.
“CL” blinking
“CL” fixed
7
Functional check in
Normal mode
Complete the door closing, if not performed: press and
keep pressed key
until the door is completely
closed.
Release key
.
Check the closing force limit for reversing, with
appropriate instrumentation.
Activate the NORMAL mode of the controller, from the
Inspection mode: press key
and check the led
NORMAL is on.
Now the controller works in Normal mode, and executes
the commands received from the MLC, as well as the
reversing from detector directly connected to the door
controller.
Perform all the functional checks with the complete
system operating in Normal mode, from the car roof or
from the landing, according to the procedure active for
the involved maintenance people.
Display visualization:
led NORMAL
on
- Table 7: configuration, learning and test sequence –
3.6
Installation trouble-shooting
The installation sequence previously reported describes all the steps that have to be executed to operate a
correct and complete set-up of the door system.
In case of issues, or if anomalous behaviours happen during the installation, please refer to the paragraph
6.2 “Troubleshooting (FAQ)”. For any alarms, please refer to the paragraph 6.1 “Alarms”.