Computec
CDD5.0
EN
CDD 5.0: user manual – Rev.01
Page 46/63
5.7.3
PC45: Door closed Reduced torque activation delay
This parameter permits to change the activation delay for the reduced torque parking, as described in the
previous paragraph.
PC45 Parameter
Range
Default value
Description
Reduced torque
parking
activation delay
[ 5 ; 305 ] s
90s
The delay is reset every time that the door drive
detects a change in DCC (or RSC if PC99=0) commands.
During the reduced torque parking phase, if the DCC
(or RSC if PC99=0) commands from OFF to ON, the
controller returns to park with nominal torque, and the
delay restarts
5.8
Particular Parameters
5.8.1
PC43: Door open parking with reduced torque
This parameter permits to enable the opening parking without torque applied to the motor. The are some
field installations with landing manual swing doors, and car automatic sliding doors, the normally park at
the floor with the car door opened to permit the manual opening of the landing swing door.
This condition, similarly to the closed parking management, implies a continuous torque applied to the
motor. To avoid this it is possible to enable this function.
Parameter value
Notes
00 = OP parking with
reduced torque NOT
ACTIVE
(default value)
The controller, during the OP parking phase, keeps always active the parking torques
to the motor.
01 = OP parking with
reduced torque ACTIVE
The controller activates the OP reduced torque parking function
5.8.2
Reduced Speed value
This parameter allows to change the reduced speed value, used for the following movements:
-
Power-on synchronization trip
-
Learning trip
-
Reduced speed trips (when RSC is active)
It is accessible only by external handset device: Main Menu
Advanced Settings
Reset speed. The table
below reports the parameter details:
Parameter
Range
Default value
Reduced speed
[0.05 ; 0.25 ] m/s
0.07 m/s