Computec
CDD5.0
EN
CDD 5.0: user manual – Rev.01
Page 31/63
N°
RANGE
DEFAULT
Name
Values Description
26
[0 ; 2]
1
Installed skate type
00 = S20
01 = S90
02 = S120
27
[0 ; 1]
0
Closing force detection when RSC active
00 = closing force detection DISABLED
01 = closing force detection ENABLED
32
[0 ; 1]
0
AUXC input options
00 = disabled
01 = partial opening floor input
33
[0 ; 5]
2
Speed profile
00 = 50%
01 = 75%
02 = 100%
03 = 125%
04 = 150%
34
[ 0 : 2]
0
RVS output signal type
00 = active until DOC command from MLC.
01 = active until reopening completed
02 = active for 0.5s
36
[0 ; 1]
0
Maximum opening power
(to be enabled only if strictly necessary because
accelerate the system wear)
00 = disabled
01 = enabled
37
[0 ; 1]
1
DOS output activation without
commands from MLC
00 = DOS active only if DOC active
01 = DOS active also in case of manual
opening
38
[5 ; 40]
25
Door opened DOS activation tolerance
Expressed in mm
39
[0 ; 1]
0
Opening profile performances
reduction, in front of motor overheating
00 = disabled
01 = enabled
42
[0 ; 1]
1
Closing force detection limit auto-tuning
00 = disabled
01 = enabled
43
[0 ; 1]
0
Door opened parking without torque
00 = disabled
01 = enabled
44
[1 ; 10]
02 (STD)
07 (EXP)
Clutch relaxing tolerance during CL
parking with closed skate
Expressed in mm, adjustable with 1mm step.
45
[5 ;305]
30
Clutch relaxing activation delay during
CL parking with closed skate
Expressed in %: 0%=5s, 100%=305s.
Default 30%=90s. Step 1%=3s
62
[-50;+50]
0
Opening deceleration offset
Expressed in mm
63
[-50;+50]
0
Closing deceleration offset
Expressed in mm
64
[0 ; 99]
18
Opening final low speed
Expressed in %. The value can change based
on the speed profile selected
70
-
-
Speed profiles reset
-
90
0,1,2,3,
4,12,13
0
Installed motor type
0 = self-recognized
1= Moog 1Nm
2 = Moog 2Nm
12 = SG80K
13 = SG120K
20 = SN40(15:1) +Enc100
21 = SN31(15:1)+Enc100
23 = SN22,6(7:1)+Enc100
91
1,2,12,13,
20, 21,23
-
Recognized motor type
Refer to the previous parameter values
99
[0 ; 2]
0
MLC commands interface logic
0 = DOC DCC RSC in normal logic, RSC is forced
closing signal
1 = DOC DCC RSC in reversed logic, RSC is a
reduced speed movement enable signal
2 = DOC DCC RSC in normal logic, RSC is a
reduced speed movement enable signal
- Table23: parameter list of the CDD5.0 door drive -