Error messages 146
2.
Be sure each fan cable is properly connected, if applicable, and each fan is properly seated.
3.
If the problem persists, replace the failed fans.
1611- Power Supply Zone Fan Assembly Failure Detected. Either...
...the Assembly is not installed or multiple fans have failed.
Audible Beeps
: None
Possible Cause
: Required fans are missing or not spinning.
Action
:
1.
Check the fans to be sure they are installed and working.
2.
Be sure the assembly is properly connected and each fan is properly seated.
3.
If the problem persists, replace the failed fans.
4.
If a known working replacement fan is not spinning, replace the assembly.
1611-Power Supply Zone Fan Assembly Failure Detected. Single fan...
...failure. Assembly will provide adequate cooling.
Audible Beeps
: None
Possible Cause
: Required fan is not spinning.
Action
: Replace the failed fan to provide redundancy, if applicable.
1611-Primary Fan Failure (Fan Zone System)
Audible Beeps
: None
Possible Cause
: A required fan is not spinning.
Action
: Replace the failed fan.
1611-Redundant Fan Failure (Fan Zone System)
Audible Beeps
: None
Possible Cause
: A redundant fan is not spinning.
Action
: Replace the failed fan.
1612-Primary Power Supply Failure
Audible Beeps
: 2 short
Possible Cause
: Primary power supply has failed.
Action
: Replace power supply.
Содержание ML570 - ProLiant - 1 GB RAM
Страница 29: ...Diagnostic flowcharts 29...
Страница 33: ...Diagnostic flowcharts 33 Server and p Class server blade POST problems flowchart...
Страница 38: ...Diagnostic flowcharts 38 c Class server blade fault indications flowchart...
Страница 197: ...Acronyms and abbreviations 197 VCRM Version Control Repository Manager VGA video graphics array...