IE-GPR-LP040-03
35
6.2. Setting of the data logger parameters
If you require sending of the warning SMS messages by the modem (for example in the case
of exceeding of the alarm limits), you will have to set these data logger parameters at least:
the data logger must be switched on
the alarm conditions must be set with desired means for all monitored channels
the alarm evaluating must be enabled for all monitored channels
If you use GPRS connection for communication with the data logger, you will be allowed to
set up the data logger remotely by using the program for data loggers. For the remote connection
you must select the item
Select port manually
in the window
File / Options / Communication
and
confirm it with pressing
OK
button. Then select the item
Configuration / Device setting
in the main
menu. Choose the correct communication port name from the displayed list.
If you don’t use GPRS connection for communication with the data logger, you will be
allowed to set up the data logger locally via the proper communication adapter (COM adapter, USB
adapter). Use the program for data loggers to set up data logger.
Attention!
The serial communication interface of data logger Gxxxx is out of service
while the data logger is connected with a computer via a USB communication cable. It
means that communication between the data logger and connected GPRS modem will
not proceed during this period.
6.3. Setting of the modem using the setting cable
If GPRS connection isn’t available, you will have to use the setting cable for setting up the
modem with no limitations. In this case, the program for data loggers must be run with the
parameter
/service
. The available way how to achieve it: click on the button
Start
, select the item
Run...
, then select the item
Browse...
, find the program
LOGGER.EXE
in your drive (if the
destination of this program wasn’t changed during installation, it will be placed in the directory
C:\Program Files\CometLoggers\Logger\Logger.exe
), select it by using the mouse and click on the
button
Open
. In the displayed field
Open
, write the char space followed by parameter
/service
at
the end of displayed path (past the quotation mark). Then click on the button
OK
. After program
start, the submenu
Service
should appear in the main menu. Select the item
M2M modem
in the
submenu
Service
. Choose the correct COM port number and confirm it with pressing
OK
button.
Now you can set up all modem parameters with no limitations.