DIP switch settings overview - Function setting
DIP switch 13 is located on the hydraulic module main control board and allows configuration of additional heating source thermistor
installation, the second inner backup heater installation, etc.
WARNING
Switch off the power supply before opening the switch box service panel and making any changes to the DIP switch settings.
DIP
switch
ON = 1
OFF = 0
Factory
configuration
S1
1 Reserved
Reserved OFF
2 Solar
YES
Solar
NO OFF
3 / 4
3 = OFF
4 = OFF
0/0 = IBH and AHS not present
0/1 = AHS present (heating mode)
1/0 = IBH present
1/1 = AHS present (heating and DHW)
DIP
switch
ON = 1
OFF = 0
Factory configu-
ration
S2
1
Pump P_o
does NOT activate every 6
hours
Pump P_o
activates every 6 hours
OFF
2
TBH not present
TBH present
OFF
3 / 4
3 = OFF
4 = ON
0/0 = variable speed pump (max 8.5mt)
0/1 = fixed speed pump
1/0 = fixed speed pump (reserved)
1/1 = variable speed pump (max 9mt)
AHS additional heating source
IBH external backup heater (optional)
TBH Storage tank electric heater
P_o external
pump
10 START-UP AND CONFIGURATION
Содержание WSAN-YMi 21
Страница 1: ...WSAN YMi 21 81 MANUAL...
Страница 43: ...43 Hydraulic module 5 7 9 kW 12 14 16 kW...
Страница 53: ...53 P 5 7 9 kW 12 14 16 kW...
Страница 112: ...112 1 phase 5 7 9KW 15 ELECTRICAL SCHEMA...
Страница 113: ...113 1 phase 12 14 16kW...
Страница 114: ...114 3 phase 12 14 16kW 15 ELECTRICAL SCHEMA...
Страница 134: ...134 Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions Structure menu...
Страница 153: ...153 20 CONTROLLER NAVIGATION MENU...
Страница 154: ...154...