127
PLC
:
Parameter
setting 2
BIT15
Supports backup heater (IBH)
BIT14
IBH supports heating
BIT13
IBH supports water heating
BIT12
Supports AHS
BIT11
AHS supports heating
BIT10
AHS supports water heating
BIT9
Supports solar energy module
BIT8
Reserved
BIT7
Reserved
BIT6:
Reserved
BIT5:
Reserved
BIT4:
Reserved
BIT3:
Reserved
BIT2:
Reserved
BIT1:
Reserved
BIT0: Reserved
212 (PLC: 40213)
dT5_On
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
213 (PLC: 40214)
dT1S5
Default setting: 10°C, range: 5~20°C, setting interval: 1°C
PLC
T_Interval_DHW
Default setting: 5 min, range: 5~30 min, setting interval: 1 min
215 (PLC: 40216)
T4DHWmax
Default setting: 43°C, range: 35~43°C, setting interval: 1°C
216 (PLC: 40217)
T4DHWmin
Default setting: -10°C, range: -25~5°C, setting interval: 1°C
217 (PLC: 40218)
t_TBH_delay
Default setting: 90 min, range: 0~240 min, setting interval: 5 min
218 (PLC: 40219)
dT5_TBH_off
Default setting: 5°C, range: 0~10°C, setting interval: 1°C
219 (PLC: 40220)
T4_TBH_on
Default setting: 5°C, range: -5~20°C, setting interval: 1°C
220 (PLC: 40221)
T5s_DI
Temperature of the disinfection water tank, range: 60~70°C, default setting: 65°C
221 (PLC: 40222)
t_DI_max
Maximum disinfection duration, range: 90~300 min, default setting: 210 min
222 (PLC: 40223)
t_DI_hightemp
Disinfection high temperature duration, range: 5~60 min, default setting: 15 min
223 (PLC: 40224)
t_interval_C
Time interval of compressor start-up in cooling mode; range: 5~30 min, default setting: 5 min
224 (PLC: 40225)
dT1SC
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
225 (PLC: 40226)
dTSC
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
226 (PLC: 40227)
T4cmax
Default setting: 43°C, range: 35~46°C, setting interval: 1°C
227 (PLC: 40228)
T4cmin
Default setting: 10°C, range: -5~25°C, setting interval: 1°C
228 (PLC: 40229)
t_interval_H
Time interval of compressor start-up in the heating mode; range: 5~60 min, default setting: 5 min
229 (PLC: 40230)
dT1SH
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
230 (PLC: 40231)
dTSH
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
231 (PLC: 40232)
T4hmax
Default setting: 25°C, range: 20~35°C, setting interval: 1°C
232 (PLC: 40233)
T4hmin
Default setting: -15°C, range: -25~5°C, setting interval: 1°C
233 (PLC: 40234)
T4_IBH_on
Ambient temperature for enabling the hydraulic module auxiliary electric heating IBH, range: -15~10°C;
default setting: -5°C
234 (PLC: 40235)
dT1_IBH_on
Temperature return difference for enabling the hydraulic module auxiliary electric heating IBH, range:
2~10°C; default setting: 5°C
235 (PLC: 40236)
t_IBH_delay
Delay time of enabling the hydraulic module auxiliary electric heating IBH, range: 15~120 min; default
setting: 30 min
236 (PLC: 40237)
t_IBH12_delay
When IBH1 is enabled, the default time for enabling IBH2, range: 5~30 min, default setting: 5 min
237 (PLC: 40238)
T4_AHS_on
Ambient temperature for enabling the external heater AHS, range: -15~10°C, setting interval: -5°C
238 (PLC: 40239)
dT1_AHS_on
Temperature return difference for enabling the external heater AHS, range: 2~10°C; default setting: 5°C
239 (PLC: 40240)
dT1_AHS_off
Temperature return difference for closing the external heater AHS, range: -5~0°C; default setting: 0°C
240 (PLC: 40241)
t_AHS_delay
Delay time for enabling the external heater AHS, range: 5~120 min; default setting: 30 min
Содержание WSAN-YMi 21
Страница 1: ...WSAN YMi 21 81 MANUAL...
Страница 43: ...43 Hydraulic module 5 7 9 kW 12 14 16 kW...
Страница 53: ...53 P 5 7 9 kW 12 14 16 kW...
Страница 112: ...112 1 phase 5 7 9KW 15 ELECTRICAL SCHEMA...
Страница 113: ...113 1 phase 12 14 16kW...
Страница 114: ...114 3 phase 12 14 16kW 15 ELECTRICAL SCHEMA...
Страница 134: ...134 Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions Structure menu...