7.1 dT1_IBH_ON
The temperature difference betw een T1S and T1 for
starting the backup heater.
5 2
10 1
℃
7.2 t_IBH_DELAY
The time that the compressor has run before the first
backup heater turns on
30 15
120 5 MIN
7.3
T4_IBH_ON
The ambient temperature for starting the backup heater
-5
-15
10
1
℃
7.4 dT1_AHS_ON
The temperature difference betw een T1S and T1B for
turning the additional heating source on
5 2
10 1
℃
7.5 t_AHS_DELAY
The time that the compressor has run before starting the
additional heating source
30 5
120 5
MIN
7.6 T4_AHS_ON
The ambient temperature for starting the additional
heating source
-5 -15
10 1
℃
8.1 T1S_H.A_H
The target outlet w ater temperature for space heating
w hen in holiday aw ay mode
25 20 25 1
℃
8.2 T5S_H.A_DHW
The target outlet w ater temperature for domestic hot
w ater heating w hen in holiday aw ay mode
25 20 25 1
℃
Code
State
Default Min
max
setting
interval
unit
12.1
PREHEATING FOR
FLOOR T1S
The setting temperature of outlet w ater during first preheating
for floor
25 25 35 1 C°
12.3 t_FIRSTFH
The time last for preheating floor
72
48
96
12 HOUR
12.4 t_DRYUP
The day for w arming up during floor drying up
8
4
15
1
DAY
12.5 t_HIGHPEAK
The continue days in high temperature during floor drying up
5
3
7
1
DAY
12.6 t_DRYD
The day of dropping temperature during floor drying up
5
4
15
1
DAY
12.7 T_DRYPEAK
The target peak temperature of w ater flow during floor drying
up
45 30 55 1 C°
12.8 START TIME
The start time of floor drying up
*
0:00 23:30 1/30 h/min
12.9 START DATE
The start date of floor drying up
The
present
date
1-1-
2000
31-12-
2099
1-1-
2001
d/m/y
13.1
AUTO RESTART
COOL/HEAT MODE
Enable or disable the auto restart cooloing/heating mode.
0=NON
,
1=YES
1 0 1 1 /
13.2
AUTO RESTART DHW
MODE
Enable or disable the auto restart DHW mode. 0=NON
,
1=YES
1 0 1 1
/
14.1
POWER INPUT
LIMITATION
The type of power input limitation, 0=NON, 1~8=TYPE 1~8
0
0
8
1
/
15.1 CN12 ON/OFF
Define the CN12 port,0= REMOTE ON/OFF,1= TBH ON/OFF
0
0
1
1
/
15.2 CN15
T1B
Enable or disable the T1B PROBE. 0=NON
;
1=YES
0 0 1 1 /
15.3 CN35 SMART GRID
Enable or disable the SMART GRID. 0=NON
;
1=YES
0 0 1 1 /
15.4 Ta
PROBE
Choose the sensor of Ta. 0=HMI Ta on w ired controller;
1=IDU Ta connected on the mainborad of indoor unit
0 0 1 1 /
* Hour
:
the present time (not on the hour +1,on the hour +2) Minute:00
10 START-UP AND CONFIGURATION
Содержание WSAN-YMi 21
Страница 1: ...WSAN YMi 21 81 MANUAL...
Страница 43: ...43 Hydraulic module 5 7 9 kW 12 14 16 kW...
Страница 53: ...53 P 5 7 9 kW 12 14 16 kW...
Страница 112: ...112 1 phase 5 7 9KW 15 ELECTRICAL SCHEMA...
Страница 113: ...113 1 phase 12 14 16kW...
Страница 114: ...114 3 phase 12 14 16kW 15 ELECTRICAL SCHEMA...
Страница 134: ...134 Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions Structure menu...
Страница 153: ...153 20 CONTROLLER NAVIGATION MENU...
Страница 154: ...154...