38
7 TYPICAL
APPLICATIONS
NOTE
The volume of balance tank(8) should be greater than 40L (for 5~9kW unit, greater than 20L)
The drain valve (6) should be installed at the lowest positon of the system.
An independent backup heater can be selected and installed in the door.
As the temperature sensor attached in the user interface is used to detect the room temperature, the user interface (4) should be
placed in the room where floor heating loops and fan coil units is installed and away from the heating source.
Correct configuration should be applied in the user interface (see chapter Start-up and configuration/ TEMP. TYPE SETTING.).
The first setpoint is water temperature which can be set on the main page of user interface, the second setpoint is calculated from
climate related curves, the target outlet water temperature is the higher one of these two setpoints.
The unit will turn off when the room temperature reaches the target temperature.
Pump operation and space heating
The pump (1.8) and (10) will operate when there is request for heating from A and/or B. Pump (23.1) will operate when the room
temperature of zone B is lower than the set point which set in the user interface.
The outdoor unit will start operating to achieve the target water flow temperature.
Содержание WSAN-YMi 21
Страница 1: ...WSAN YMi 21 81 MANUAL...
Страница 43: ...43 Hydraulic module 5 7 9 kW 12 14 16 kW...
Страница 53: ...53 P 5 7 9 kW 12 14 16 kW...
Страница 112: ...112 1 phase 5 7 9KW 15 ELECTRICAL SCHEMA...
Страница 113: ...113 1 phase 12 14 16kW...
Страница 114: ...114 3 phase 12 14 16kW 15 ELECTRICAL SCHEMA...
Страница 134: ...134 Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions Structure menu...
Страница 153: ...153 20 CONTROLLER NAVIGATION MENU...
Страница 154: ...154...