2 SAFETY
PRECAUTIONS
•
Confirm the safety of the installation area ( walls, floors, etc. ) without hidden dangers such as water, electricity, and gas.Before
wiring/pipes.
•
Before installation , check whether the user's power supply meets the electrical installation requirements of unit ( including
reliable grounding , leakage , and wire diameter electrical load, etc. ). If the electrical installation requirements of the product are
not met, the installation of the product is prohibited until the product is rectified.
•
When installing multiple air conditioners in a centralized manner, please confirm the load balance of the three-phase power
supply, and multiple units are prevented from being assembled into the same phase of the three-phase power supply.
•
Product installation should be fixed firmly, Take reinforcement measures, when necessary.
NOTE
About Fluorinated Gasses
This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas and the amount, please refer to the
relevant label on the unit itself. Compliance with national gas regulations shall be observed.
Installation, service, maintenance and repair of this unit must be performed by a certified technician.
Product uninstallation and recycling must be performed by a certified technician.
If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months. When the unit is checked
for leaks, proper record-keeping of all checks is strongly recommended.
REFRIGERANT INFORMATION
This product has the fluorinated gas, it is forbidden to release to air.
Refrigerant type: R32;
Volume of GWP: 675.
GWP=Global Warming Potential
Model
Refrigerant/kg Tonnes
CO
2
equivalent
5kW 2.00
1.35
7kW 2.00
1.35
9kW 2.00
1.35
12kW 2.80
1.89
14kW 2.80
1.89
16kW 2.80
1.89
Factory charged refrigerant volume in the unit
CAUTION
This air-conditioning unit is a hermetically sealed equipment that contains fluorinated greenhouse gases.
Only certificated person is allowed to do installation, operation and maintenance.
Frequency of Refrigerant Leakage Checks
For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO
2
equivalent or more,but of less than 50
tonnes of CO
2
equivalent,at least every 12 months, or where a leakage detection system is installed, at least every 24 months.
Only certificated person is allowed to do installation, operation and maintenance.
Содержание WSAN-YMi 21
Страница 1: ...WSAN YMi 21 81 MANUAL...
Страница 43: ...43 Hydraulic module 5 7 9 kW 12 14 16 kW...
Страница 53: ...53 P 5 7 9 kW 12 14 16 kW...
Страница 112: ...112 1 phase 5 7 9KW 15 ELECTRICAL SCHEMA...
Страница 113: ...113 1 phase 12 14 16kW...
Страница 114: ...114 3 phase 12 14 16kW 15 ELECTRICAL SCHEMA...
Страница 134: ...134 Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions Structure menu...
Страница 153: ...153 20 CONTROLLER NAVIGATION MENU...
Страница 154: ...154...