Installation
Do not install the unit in a place with much oil, steam, sulfide gas.
Otherwise, the product may deform and fail.
2) Check that all the components listed below are present.
3) Circuit of Wired Remote Controller is low voltage circuit. Never
connect it with a standard 220V/380V circuit or put it into a same
Wiring Tube with the circuit.
4) The shielded cable must be connected stable to the ground, or
transmission may fail.
5) Do not attempt to extend the shielded cable by cutting, if it is
necessary, use Terminal Connection Block to connect.
6) After finishing connection, do not use Megger to have the
insulation check for the signal wire
No.
Name
Qty.
Remarks
1 Wired
Controller
1
2
Cross round head wood mounting screw
3
For Mounting on the Wall
3
Cross round head mounting screw
2
For Mounting on the Electrical Switch Box
4
Installation and Owner's Manual
1
5 Plastic
bolt
2
This accessory is used when install the centralized
control inside the electric cabinet
6
Plastic expansion pipe
3
For mounting on the Wall
User interface
COMMUNICATION
NOTE
Use shielded wire and earth the wire.
This equipment supports MODBUS RTU communication
protocol. - See ATTACHMENTS
Wire type
5 wire shielded cable
Wire section(mm
2
) 0.75~1.25
Maximum wire length(m)
50
Input voltage (A/B)
13.5VAC
9 ELECTRICAL
CONNECTIONS
Содержание WSAN-YMi 21
Страница 1: ...WSAN YMi 21 81 MANUAL...
Страница 43: ...43 Hydraulic module 5 7 9 kW 12 14 16 kW...
Страница 53: ...53 P 5 7 9 kW 12 14 16 kW...
Страница 112: ...112 1 phase 5 7 9KW 15 ELECTRICAL SCHEMA...
Страница 113: ...113 1 phase 12 14 16kW...
Страница 114: ...114 3 phase 12 14 16kW 15 ELECTRICAL SCHEMA...
Страница 134: ...134 Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions Structure menu...
Страница 153: ...153 20 CONTROLLER NAVIGATION MENU...
Страница 154: ...154...