C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
TSL Vertical Stack
R e v. : 0 4 / 2 4 / 2 0 1 9
54
C l i m a t e M a s t e r Wa t e r - S o u rc e H e a t P u m p s
Coax Water Pressure Drop
Hybrid Unit Correction Table
Model
GPM
Pressure Drop, PSI
PD Added for
Add for MWV
30°F
50°F
70°F
90°F
TSM/TSL09
1.5
1.1
0.5
0.4
0.3
0.3
2.3
1.8
1.6
1.4
1.5
0.5
3.0
4.7
3.6
3.0
3.1
0.6
TSM/TSL12
1.8
3.4
2.3
2.2
2.1
0.4
2.6
5.6
4.2
4.0
3.7
0.5
3.5
7.8
7.7
6.2
5.5
0.7
TSM/TSL15
2.3
2.3
2.1
2.0
1.9
0.2
3.5
5.0
4.2
4.2
3.9
0.3
4.5
8.3
7.1
6.9
6.6
0.4
TSM/TSL18
3.4
2.2
1.5
1.4
1.1
0.3
5.1
4.2
3.3
2.4
2.8
0.5
6.8
6.7
4.4
4.2
4.0
0.7
TSM/TSL24
4.0
0.9
0.5
0.4
0.3
0.4
6.0
2.3
2.2
1.8
1.8
0.6
8.0
5.0
4.3
3.8
3.2
0.8
TSM/TSL30
4.0
0.9
0.5
0.4
0.3
0.4
6.0
2.3
2.2
1.8
1.8
0.6
8.0
5.0
4.3
3.8
3.2
0.8
TSM/TSL36
4.5
2.8
0.9
0.8
0.8
0.4
6.0
3.8
2.4
2.2
2.1
0.7
9.0
7.4
4.7
4.3
4.0
0.9
Table 16
Size
Hydronic
Coil Static
TSL09
0.1
TSL12
0.1
TSL15
0.1
TSL18
0.15
TSL24
0.15
TSL30
0.15
TSL36
0.2
% of
Nominal
(rated)
SCFM
Heating
Capacity
70
0.8
75
0.8
80
0.9
85
0.9
90
0.9
95
1.0
100
1.0
105
1.0
Entering
Air DB
(°F)
Heating
Capacity
45
1.65
50
1.52
55
1.39
60
1.25
65
1.12
68
1.04
70
1
75
0.85
80
0.72
Blower Motor
Correction Table
Air Flow
Correction Table
Entering Air
Correction Table