5-95
Cisco 7600 Series Router Installation Guide
OL-4503-26
Chapter 5 Removal and Replacement Procedures
Removing and Replacing the Power Supply
Figure 5-92
DC-Input Wire Connections for 2700-W DC-Input Power Supply for Left Side of Power
Bay
d.
From the left side of the power supply, connect the DC-input wires to TB1 (
Figure 5-91
and
Figure 5-92
) in this order:
Negative (-)
Positive (+)
Note
When you tighten the terminal nuts, make sure they are snug. Do not over tighten them.
Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can
break the terminal block (Maximum torque: 36 inch-pounds).
Place and secure left and right inner terminal block cover.
e.
Secure outer block cover.
Step 9
Wire for 4000 W (left side of power supply bay) as follows:
a.
Place both plastic insulators over the terminal areas, aligning the circular holes in insulating cover
with terminal posts. The protective end flap on the plastic cover is opposite the wire entry area. The
protective end flap must fold down and cover the open side of the terminal (opposite side from wire
entry).
b.
Wrap the large perforated flaps around each pair of conductors, inserting each locking tab into rear
of slot. Pull the tab until the cover is secured around the power cabling trim and discard excess tab
plastic.
c.
From the left side of the power supply, connect the ground wire to the ground (
Figure 5-93
).
114010
3
INPUT OK
FAN
OK
OUTPUT
FAIL
I
0
1
2
Captive
installation
screw
(+) Positive
( - ) Negative
Power
switch
( ) Ground
(+) Positive
( - ) Negative
Power leads
attached to
terminal block
Terminal
block cover
Plastic
insulator