5-30
Cisco 7600 Series Router Installation Guide
OL-4503-26
Chapter 5 Removal and Replacement Procedures
Removing and Replacing the Power Supply
Step 6
Remove the plastic insulator from over the terminal area
(
Figure 5-33
).
Step 7
Disconnect the DC-input wires from the terminal block in this order:
•
Positive (+)
•
Negative (-)
Note
You must remove DC-input wires from two terminal blocks for the 4000 W DC-input power
supply (if both terminal blocks are used).
Step 8
Disconnect the PWR-4000-DC power supply ground.
Warning
When installing the unit, the ground connection must always be made first and disconnected last.
Figure 5-33
DC-Input Wire Connections for 4000-W DC-Input Power Supply
Note
Figure 5-33
shows a 4000 W configuration that requires cable tie-wraps.
Step 9
Loosen the captive installation screw on the power supply (
Figure 5-33
).
Caution
Use both hands to install and remove power supplies. Each DC-input power supply weighs between 22
pounds (9.9 kg) and 33 pounds (15 kg).
114008