2-15
Cisco 7600 Series Router Installation Guide
OL-4503-26
Chapter 2 Preparing for Installation
Site Requirements
Table 2-13
lists the power and the heat numbers for the 10BASE Ethernet switching modules.
Table 2-14
lists the power and the heat numbers for the FlexWAN and the enhanced FlexWAN modules.
WS-X6148X2-45AF
96-port 10/100 Ethernet module
with WS-F6K-FE48X2-AF PoE
daughter card
3.07
128.94
161.18
550.41
173.31
591.84
WS-X6196-RJ-21
96-port 10/100 Ethernet module
2.74
115.08
143.85
491.25
154.68
528.22
WS-X6196-21AF
96-port 10/100 Ethernet module
with WS-F6K-FE48X2-AF PoE
daughter card
3.16
132.72
165.90
566.55
178.39
609.19
WS-X6248A-TEL
48-port 10/100 Ethernet module
(telco)
2.69
113
141.23
482.28
151.85
518.58
WS-X6348-RJ21V
48-port 10/100 Ethernet module
with WS-F6K-VPWR PoE
daughter card
2.39
100.38
125.48
428.5
134.92
460.75
WS-X6348-RJ-45
48-port 10/100 Ethernet module
2.39
100.38
125.48
428.5
134.92
460.75
WS-X6348-RJ-45V
48-port 10/100 Ethernet module
with WS-F6K-VPWR PoE
daughter card
2.39
100.38
125.48
428.5
134.92
460.75
WS-X6548-RJ-21
48-port 10/100 Ethernet module
2.90
121.80
152.25
519.93
163.71
559.07
WS-X6548-RJ-45
48-port 10/100 Ethernet module
2.90
121.80
152.25
519.93
163.71
559.07
Table 2-12
Power Requirements and Heat Dissipation—10/100 Ethernet Switching Modules (continued)
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
Table 2-13
Power Requirements and Heat Dissipation—10BASE Ethernet Switching Modules
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
WS-X6024-10FL-MT
24-port 10BASE-FL Ethernet
module
1.52
63.84
79.8
272.52
85.81
293.0