2-8
Cisco 7600 Series Router Installation Guide
OL-4503-26
Chapter 2 Preparing for Installation
Site Requirements
Table 2-5
lists the power and the heat numbers for the Policy Feature Cards (PFCs).
WS-SUP32-10GE-3B
Supervisor Engine 32 with PFC3B and
MSFC2A daughter cards
4.19
175.98
219.98
751.21
236.53
807.76
WS-SUP32-GE-3B
Supervisor Engine 32 with PFC3B and
MSFC2A daughter cards
3.69
154.98
193.73
661.57
208.31
711.37
WS-SUP720
Supervisor Engine 720 with PFC3A
daughter card and integrated MSFC3
and switch fabric
7.50
315.0
393.75
1344.66
423.39
1445.87
WS-SUP720-3B
Supervisor Engine 720 with PFC3B
daughter card and integrated MSFC3
and switch fabric
6.72
282.24
350.80
1204.81
379.35
1295.5
WS-SUP720-3BXL
Supervisor Engine 720 with PFC3BXL
daughter card and integrated MSFC3
and switch fabric
7.82
328.44
410.55
1402.03
441.45
1507.56
RSP720-3C-GE
6.90
290
362.50
1237.93
389.78
1331.11
RSP720-3CXL-GE
8.10
340.20
425.25
1452.23
457.26
1561.54
RSP720-3C-10GE
8.80
370
462.50
1579.43
497.31
1698.31
RSP720-3CXL-10GE
10
420
525
1792.87
564.51
1927.82
Table 2-4
Power Requirements and Heat Dissipation—Supervisor Engines (continued)
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
Table 2-5
Power Requirements and Heat Dissipation—Policy Feature Cards (PFCs)
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
WS-F6K-PFC3A
Policy Feature Card 3A
2.25
94.50
118.13
403.40
127.02
433.76
WS-F6K-PFC3B
Policy Feature Card 3B
1.47
61.74
77.18
263.55
82.98
283.39
WS-F6K-PFC3BXL
Policy Feature Card 3BXL
2.57
107.94
134.93
460.77
145.08
495.45