78-16033-01
Chapter 4 Provisioning Using ASH and SNMP
Set Password
4.9 Set Password
To restrict access to the ONS 15216 EDFA2, use the user passwd set command to change the default
user password. The password must be a string of up to 10 characters, where at least 2 are non-alphabetic
characters and at least 1 is a special character. With the exception of the administrator access level
(read_write_admin), users can only modify their own passwords. For additional information on user
levels, refer to
Table 6-1 on page 6-1
.
Example 4-9
displays the command.
Example 4-9
Changing Current User’s Password
ash:hostname:ONS15216 EDFA2> user passwd set
cerent15216Edfa
PowerBusDCVolt
ageMin
Power bus
minimum
voltage
Integer
(350 to
700, 400
default)
Read-write
Minimum allowable power bus DC
voltage. The default minimum power bus
voltage is set at –40 VDC. Valid entries
are between 350 and 700 and are in
negative volts times 10. For example, if
the voltage required is –40 VDC, the
power bus setting is 400.
The power bus threshold has a 1.0V
tolerance and a 1.0V hysteresis. There is
a potential ±1.5V inaccuracy in the
ONS 15216 EDFA2 voltage
measurement. If the minimum threshold
is configured at 400 (-40 VDC), the
alarm will not raise until the voltage
measures below -39 VDC and will not
clear until the voltage measures above
-41 VDC.
cerent15216Edfa
PowerBusDCVolt
ageMax
Power bus
maximum
voltage
Integer
(350 to
700, 570
default)
Read-write
Maximum allowable power bus DC
voltage. The default maximum power bus
voltage is set at –57 VDC. Valid entries
are between 350 and 700 and are in
negative volts times 10. For example, if
the voltage required is –57 VDC, the
power bus setting is 570.
The power bus threshold has a 1.0V
tolerance and a 1.0V hysteresis. There is
a potential ±1.5V inaccuracy in the
ONS 15216 EDFA2 voltage
measurement. If the maximum threshold
is configured at 570 (-57 VDC), the
alarm will not raise until the voltage
measures above -58 VDC and will not
clear until the voltage measures below
-56 VDC.