AC Faults
Before introduce any fault to the emulated grid, set any grid using Grid Mode in the AC
Operation tab. The faults are going to be done in this emulated introduced grid.
-
A:
Selection of the fault. By selecting each fault, the corresponding part is going to be
illuminated.
-
B:
Voltage Dip configurations. Introduce the percentage of the dip, the angle of each
phase and the ramps. Note that 0% means 0V and 50% is the half of the current voltage.
Press send once the parameters are introduced.
-
C:
Under/Over voltage configurations. Introduce the percentage and the ramps for all
the phases. The maximum over voltage is 120%. Press send once the parameters are
introduced.