Connection
3.4.1.
Earth protection
As a device with class l protection against electric shocks, it is essential to install a protective
earth wire (connect earth
). Connect the protection earth wire to the terminal (
X5
) before
connecting the grid to the grid emulator input.
On the other hand, connect the protection earth wire to the terminal (
X10
) before connecting
the EUT to the grid emulator output.
3.4.2.
Input connection, terminals (X1 to X5).
Connect the grid cables
R
,
S
,
T
and
N
to the terminals (
X1
), (
X2
), (
X3
) and (
X4
) respectively. This
connection must always be done according to the label placed under the input screw terminals.
In case of discrepancies between labelling and this manual instruction,
the label information
will always prevail
.
3.4.3.
External isolation transformer
In case of isolation transformer, connect grid cables (R, S, T without neutral) to the primary of
the transformer (U1, V1, W1) and secondary of the transformer (U2, V2, W2, N2) to the input
terminals (
X1
), (
X2
), (
X3
) and (
X4
) of GE.
The ground cable (PE) of the main grid must be connected to ground transformer
terminal (yellow-green) and ground GE terminal (X5) in all cases
.