Positioning User Manual
26
3)
Positioning Special Module (PLC-S) Configuration
A)
How to configure X Axis Parameter
The default setting for the X Axis is as follows.
B)
How to configure X Axis Position Data
C)
How to write a Scan Program
1)
For the initial run, the current position value is configured as 1,000.
-
POSCTRL command is used.
2)
When M00 Bit is turned on (by Shift + Enter), ABS position data will be executed.
Item
Setting Value
Description
Pulse Output Method
High Active
Select a desired pulse output type
Bias Speed(PPS)
100
Initial speed for the positioning
Speed Limit(PPS)
1,000
Maximum speed for the positioning
Acc/Dec Time 1
1,000
The time taken for the speed to increase or
decrease from 0 to the speed limit
Acc/Dec Time 2
1,000
Acc/Dec Time 3
1,000
Acc/Dec Time 4
1,000
Position
Data No.
Control
Pattern
Interpolation
Acceleration
Time
Deceleration
Time
Control
Code
Dwell
Time
Operation
Speed
Target
Address
1
Single
Step
Non-
Interpolation
No. 1
No. 1
ABS
0
1,000
5,000