5
12/03/12
7.
Do not store near combustible materials boiler.
8.
The device is powered by electricity 230V/50Hz. Improper repair or improper installation
can cause danger to life by electric shock.
9.
Do not block ventilation openings or close the supply and exhaust boiler room.
10.
Regularly clean the boiler, burner and the exhaust.
Failure to follow these guidelines risk damage to health or life threatening.
Safe distance from flammable materials.
−
during installation and use of the burner must be kept 200 mm distance from the
mid-combustible materials.
−
during installation and use of the burner must be kept 400 mm distance from
flammable materials, especially C3 (paper, wood, plastic, etc.;)
−
if the flammability of materials is very large distances must be doubled
.
Table:
Flammability class:
Materials
A
–
Non-flammable
Sandstone, concrete, bricks, plaster made of non-combustible material, ceramic tiles, granite
B –
Slow-burning
The surface of cement-wood, fiberglass
C
1
– hard-burning
Beech, oak wood, plywood
C
2
– medium-burning
Pine, larch wood, spruce wood, cork, rubber base
C
3
– easy-burning
asphalt, celluloid, polyurethane, polystyrene, plastic, PVC
5. Burner’s installation and requirements.
Tips for Installer:
During the installation of the burner as well as its use must comply with applicable rules:
- supply and exhaust ventilation, boiler room,
- flue gas canals
- technical equipment and water heating systems security.
- technical conditions of boiler rooms .
Location and mounting requirements
“MOC” burner is designed for installation in solid fuel boilers or oil boilers installed in rooms that
meet the conditions of the boiler room built for solid fuel.
- The room where the burner is to be installed must be dry, free from the vapors of flammable and
corrosive substances.
- In the surroundings of the burner temperature should not exceed 50 ° C and should not be less than
0 ° C.
- The air humidity should be in the range from 10% to 80% without condensation.
Installation of the burner should be preceded by checking the possibilities of adapting the boiler to
the burner and the fulfillment of the requirements:
- Location of the burner assembly must take into account conduct maintenance and service. It
should provide about 50 cm. free space around the burner.