11
12/03/12
Starting dose.
For a normal ignition is needed about 0,20-0,3 L pellets. Time must be chosen so the feeder at the
start that the amount of pellet was appropriate.
Firing time.
This is the time after which the controller if you do not see the flame on the burner complete the
process of firing, ie, off lighter. Please set it as short as possible because it increases the life of the
heater. As a rule, is 6-10 min.
Number of attempts to ignite.
Number of attempts to ignite after which it will not ignite if the driver will go into alarm. Standard
setting 2 sample. Do not set more because too much fuel to the burner may cause interference to the
device.
Photocell.
The task of the photocell (photocell) is to show the initiation of the ignition burner as well as being
a source of information for the controller that the burner is extinguished.
Photocell settings depending on the type of controller are:
- The threshold of firing, ie, the reading lights above which the regulator considers that the ignition,
- The type of photocell,
- Its sensitivity.
The amount of fuel and power fan
Time of the feeder as well as fan power should be chosen so that the flame was
stable, and its colour should be bright red. White flame indicates too much aeration chamber of the
burner, a dark red to a lack of air.
Each time after changing settings in the controller must wait a few minutes to observe the changes.
The
fine
adjustment
is
recommended
for
analysis
of
exhaust.
To adjust the power of the burner, set working hours and time off work enough to feed pellet was
delivered within 1 hour to the burner.
From 1 kg of pellets can be obtained within 4-5kW. So for example, 25 kW power must give at
least 5 kg of fuel during 1h. Regulators are adjustable by the minimum and maximum employment
as well as modulated.
Startup and shut down the burner.
Starting the burner will start automatically when you press START button on the controller.
Combustion will take place automatically, ie, he will seek to maintain a preset temperature is
exceeded after a self-extinguish. When the boiler temperature drops below the histeresis value set
will restart the burner.
To switch off, go to the stop function on or off the controller.
The detailed methods of setting and description of the parameters refer to the manual controller (RK
2006LP or Ecomax 800P).
7
Maintenance.
Cleaning the outside cover.
Clean the exterior cover of the burner with a slightly damp cloth and detergent agents.
Ash removal:
Empty the ash, as few or several days depending on the load at which the boiler is working, ash
content in the fuel, the size of the ash in the boiler.
If the burner creates a gangrene (“ash stone”) should be removed because it may hinder the lighting
and proper combustion. With poor quality pellets this should be checked every 1-3 days.
With good quality pellets on the burner should not create a gangrene (lumps of molten ash) and then
control and cleaning can be done every few weeks.