6.1 Schedule of Function Parameters
6.1 Schedule of Function Parameters
4:
AFm:(0~AFM
)=(0.00~
)
DFm:(0~DFM
)=(0.00~
)
5:
AFm:(0~AFM
)=(0.00~800V)
DFm:(0~DFM
)=(0.00~800V)
6:
AFm:(0~AFM
)=(0.00~10.00V)
DFm:(0~DFM
)=(0.00~10.00V)
7:
AFm:(0~AFM
)=(0.00~10.00V)
DFm:(0~DFM
)=(0.00~10.00V)
Output voltage
Upper limit value
Maximum/Rated output voltage
Upper limit value
Maximum/Rated output voltage
Bus bar voltage
Upper limit value
Upper limit value
PID given value
Upper limit value
Upper limit value
PID feedback value
Upper limit value
Upper limit value
F5.11 AFM gain setting Setting range: 20~200% Default value: 100%
F5.12 Remain
F5.13 DFM gain setting Setting range: 20~200% Default value: 100%
F5.14 Remain
Parameter F5.11 defines the upper limit value for analog output AFM. If the default
value is 100% and the range of output voltage/current is 0.00~10.00V/0.00~20.00mA,
then the voltage and current output will be selected by the jumper.
AFM output = (0~10V/0~20mA)
F5.11
Maximum value
10V/20mA
Parameter F5.13 define the upper limit value for digital output DFM. If the default
value is 100%, then the range of output frequency will be 0.0~10.0KHz.
DFM output = (0~10KHz)
F5.13 (Maximum value =20KHz)
F5.15 Combined feed path setting Setting range: 000~666 Default value: 000
This parameter is used to set the frequency feed path.
LED units digit: Operation figure 1
0: Keyboard potentiometer
1: Digital feeding 1
2: Remain
3: Digital feeding 3
4: AVI
5: ACI
6: Digital feeding 2
LED tens digits: Operation figure 2
0: Keyboard potentiometer
1: Digital feeding 1
2: Remain
3: Digital feeding 3
4: AVI
5: ACI
6: Digital feeding 2
LED hundreds digit: Operation figure 3
0: Keyboard potentiometer
1: Digital feeding 1
2: Remain
3: Digital feeding 3
4: AVI
5: ACI
6: Digital feeding 2
LED thousands digit: Remain