6.1 Schedule of Function Parameters
6.1 Schedule of Function Parameters
Tips
Jog operation begins if F2.00=0 and stops if F2.11=0 according
to the starting mode.
JOG control can be performed by the operator panel, control
terminals and COM ports.
Propriety is always given to JOG frequency operation when
pressing the JOG key in any operation states.
F2.22 Acceleration time 2 Setting range: 0.0~3600.0s Default value: as per spec.
F2.23 Deceleration time 2 Setting range: 0.0~3600.0s Default value: as per spec.
F2.24 Acceleration time 3 Setting range: 0.0~3600.0s Default value: as per spec.
F2.25 Deceleration time 3 Setting range: 0.0~3600.0s Default value: as per spec.
F2.26 Acceleration time 4 Setting range: 0.0~3600.0s Default value: as per spec.
F2.27 Deceleration time 4 Setting range: 0.0~3600.0s Default value: as per spec.
F2.22~F2.27 are the acceleration/deceleration time controlled by the inverter's
external terminals through selecting "4" and "5" of the multi-function terminal
X1~X6 (F4.00~F4.05).
F2.28 1st stage speed operation frequency Setting range: 0.00~upper limiting frequency Default value: 5.00Hz
F2.29 2nd stage speed operation frequency Setting range: 0.00~upper limiting frequency Default value: 10.00Hz
F2.30 3rd stage speed operation frequency Setting range: 0.00~upper limiting frequency Default value: 20.00Hz
F2.31 4th stage speed operation frequency Setting range: 0.00~upper limiting frequency Default value: 30.00Hz
F2.32 5th stage speed operation frequency Setting range: 0.00~upper limiting frequency Default value: 40.00Hz
F2.33 6th stage speed operation frequency Setting range: 0.00~upper limiting frequency Default value: 45.00Hz
F2.34 7th stage speed operation frequency Setting range: 0.00~upper limiting frequency Default value: 50.00Hz
The above parameters are used to set 1st~7th stage frequency of programmable/multi-
stage speed operation. Refer to parameter F7.00 for details.
F2.35 Remain
F2.36 Leap frequency 1 Setting range: 0.00~upper limiting frequency Default value: 0.00Hz
F2.37 Range of leap frequency 1 Setting range: 0.00~10.00Hz Default value: 0.00Hz
F2.38 Leap frequency 2 Setting range: 0.00~upper limiting frequency Default value: 0.00Hz
F2.39 Range of leap frequency 2 Setting range: 0.00~10.00Hz Default value: 0.00Hz
F2.40 Leap frequency 2 Setting range: 0.00~upper limiting frequency Default value: 0.00Hz
F2.41 Range of leap frequency 2 Setting range: 0.00~10.00Hz Default value: 0.00Hz
The purpose of setting F2.36~F2.41 is to avoid point of resonant frequency of mechanical load so
that the three points of leap frequency of the inverter can be set. If the leap range is set to "0",
then no leap function performs at corresponding points of leap frequency
The inverter's output frequency can act leap operation near some frequency points, as shown in
Fig.6-11.
Output frequency
Leap frequency 3
Leap frequency 2
Leap frequency 1
Range of leap frequency 3
Range of leap frequency 2
Range of leap frequency 1
Frequency setting value
Fig.6-11 Leap Frequency Setting
Tips
During accelerating and decelerating operation, the inverter can
not skip leap frequency.
Do not set two leap frequency ranges overlaid or inlaid.