Copyright CPS America Co., Ltd. Page 23
ii) Secure the edge point of mounting bracket
In order to avoid the wiring box swaying due to weather, the security
screws for the wiring box must be tightening. There will be two pieces of
the M4 size screws found within accessories box. The tightening location
of mounting bracket was indicated in figure 5.4.8. Follow the below
instructions in order to complete the tightening procedures:
Figure 5.4.8: The edge point of mounting bracket
WARNING
The wiring box shall not be opened under dusty or moist weather.
Working with the exposed electrical components under in moist
weather is very dangerous, which might cause an electric shock
easily. In dusty weather, electrical components of the wiring box
might be damaged if there is heavy dust floating within air during
serving period. Please be aware and avoid.
CAUTION
It is necessary to disconnect the DC generator and AC Utility if
the wiring box is already wired with any DC or AC connection. It
is necessary to wait 5 minutes in order to ensure all the electrical
components are discharged.
ESD Protection
An ESD glove should be worn during the cable wiring, replacing
the fuses and installing the components.
iii) Turn off DC/AC disconnect switch from the wiring box as illustrated
below:
Figure 5.4.9: Turn off DC/AC disconnect switch