Copyright CPS America Co., Ltd.                                                                                            Page 15                                                     
 

 

5.3 Identify the PV Inverter 

The structure of the CPS grid-tied PV Inverter can be divided into two parts, 

main  housing  and  wiring  box  shown  in  figure  5.3.1.  The  main  housing 

contains  the  electrical  components  that  are used for  power  conversion  and 

the  wiring  box  contains  the  electrical  components  that  are  used  as  the 

connection points for DC input voltage and AC output voltage as required by 

the NEC.     

   

Figure 5.3.1: PV Inverters Structure 

 

CPS  grid-tied  PV  Inverter  can  be  identified  by  the  name  plate.  The  name 

plate  indicates  general  electrical  information  of  the  product  as  shown  in 

Figure 5.3.2: 

Main Housing 

 

Wiring Box 
 

Содержание CPS SCE4KTL-O/US

Страница 1: ...CPS SCE Series Grid tied PV Inverter CPS SCE4KTL O US CPS SCE5KTL O US CPS SCE6KTL O US CPS SCE7KTL O US Installation and Operation Manual CHINT POWER SYSTEMS AMERICA CO LTD ...

Страница 2: ...r 17 6 Wiring Box Overview 26 6 1 Hardware Structures 26 6 2 Hardware Functioning 27 6 3 Maximum AC Short Circuit Current 40 6 4 Knockouts for the AC and DC wiring 40 7 Connecting the PV Inverter 44 7 1 DC Wire Connections 44 7 2 AC Wire Connections 48 8 LCD Display and Function Structure 55 8 1 First Level Display Menu 55 8 2 Second Level Display Menu 56 8 2 1 Daily Weekly and Monthly Energy Disp...

Страница 3: ...erter or simply Inverter This PV Inverter is a highly reliable product due to its innovative design and perfect quality control Such an Inverter is used in high demand grid tied PV systems If you encounter any problems during installation or operation of this unit first check this manual before contacting your local dealer or supplier Instructions inside this manual will help you solve most instal...

Страница 4: ... and other local regulations to meet the requirements of electrical installation in the United States For the electrical installation in Canada inverter installation must be completed in accordance with applicable Canadian standards Safety Instructions This manual contains important safety instructions to minimize the hazards to people and equipments Not following the procedures and practices corr...

Страница 5: ...njury if not avoided IMPORTANT Important indicates important and useful information that the user should know about the system ESD Protection Risk of electric shock can occur when qualified service personnel are dealing with the electrical components within the PV Inverter such as wiring box An ESD glove should be worn during the wiring operation fuse replacement and component installation Tool Eq...

Страница 6: ...tion relating to other equipments installed in the PV system The following safety instruction should be followed WARNING It is necessary that only qualified personnel conduct the installation and operation of the PV Inverter Otherwise risk of damage to or destruction of part or all of the Inverter and or other equipments connected to the Inverter or personal injury due to improper installation pro...

Страница 7: ...urposes other than for which it was designed The Inverter has been used beyond its stated specifications operating parameters and application Acts of third parties atmospheric discharges excess voltage chemical influences natural wear and tear and for loss and damage in transit Improper testing operation maintenance adjustment repair or any modification of any kind not authorized in writing by the...

Страница 8: ...ltage out 208 240 277 Vac Wide MPPT voltage operating range 105 500V Integrated NEC compliant wire raceway Integrated PV system AC DC disconnect switch 4 branch circuit rated Negative and Positive fused inputs Performance Monitoring Package LCD display with side pushbutton for nighttime monitoring NEMA 3R enclosure Meets UL1741 standard ...

Страница 9: ...fficient irradiation they will generate DC power First the DC will be fed to the PV Inverter via DC distribution unit Then the Inverter converts the DC to AC and feeds AC to the Public Grid via the AC distribution unit The AC power can be used directly by the local load or it can be sold to your energy supplier The following figure shows the general picture of a grid tied PV System Figure 4 1 1 Ge...

Страница 10: ...is compatible with the local electric distribution network also called the public grid The CPS grid tied PV Inverter is designed with a transformer less topology Therefore CPS grid tied PV Inverters will not be suitable with PV modules that are required to have the negative or positive polarity of PV modules connected to the ground For such application please contact the supplier before proceeding...

Страница 11: ...Page 9 4 3 Dimensions and Weight Figure 4 3 1 Dimensions of PV Inverter Table 4 3 1 Product weight in the package Inverter Model CPS SCE4KTL O US CPS SCE5KTL O US CPS SCE6KTL O US CPS SCE7KTL O US Net Weight lbs 86 90 4 101 4 101 4 ...

Страница 12: ...s C Control Buttons They are three control buttons available to switch between each display menu and configure the settings for the LCD D DC AC Disconnect Switch It is a built in disconnect switch that is used to disconnect both the DC input and AC output power to and from the PV inverter E Hand Grip Area It is a carrying area that is used to lift up the PV Inverter For the lifting two people are ...

Страница 13: ...ill light up in green when the feed in DC voltage from PV array reaches the minimum operating voltage for the PV Inverter B Fault LED Indicator It is a red LED indicator that lights in red when the PV Inverter has a fault during startup or operating period C Communication LED Indicator It is a Green LED indicator that lights and flashes in green when there is a communication device connected and w...

Страница 14: ...play menu the user can hold the enter control button for more than two seconds until LCD displays a Lock text To release the user can presses the same control button for another two seconds again in order to release menu from the lock mode C Down Control Button The down control button is used to advance the display menu in the opposite direction to the up control button D Liquid Crystal Display LC...

Страница 15: ...kage The 3 Accessory Box contains items listed below Items Q ty Purpose Figure User s Manual 1 Installation and Operation Manual Mounting Anchor 6 For bracket installation Screw M4 6 Security Screw M4 2 For security locking to Inverter Terminal Connector See For AC DC Wires Table 5 1 2 Items in the accessory box Terminal Connectors of AC DC wires are provided for Each Inverter Model Table 5 1 3 Nu...

Страница 16: ...ue to the weight of the inverter it is recommended at least 2 people lift the PV Inverter from the packing and also for the mounting the PV Inverter on the wall CAUTION It is important to use the correct lifting point to lift the PV Inverter from the packing as any improper carrying and moving could result in serious injury or damage the unit Warning Any modification of the PV Inverter is not perm...

Страница 17: ...trical components that are used for power conversion and the wiring box contains the electrical components that are used as the connection points for DC input voltage and AC output voltage as required by the NEC Figure 5 3 1 PV Inverters Structure CPS grid tied PV Inverter can be identified by the name plate The name plate indicates general electrical information of the product as shown in Figure ...

Страница 18: ... in figure 5 3 4 This warning label is used to indicate all important notices that shall be known When you are dealing with the general utility system and DC generator read and follow all notifications from the warning label as a reminder in order to prevent any electric shock that can happen during the configuration period Figure 5 3 4 Warning Label Plate ...

Страница 19: ... sunlight because the exposure of direct sunlight may cause an internal heating and also a reduction of output power which is known as derating protection B Select a wall or solid vertical surface which is strong enough to support the inverter WARNING PV Inverter s surface and housing can become hot during operation Ensure not to install PV Inverters in a location that contains any flammable mater...

Страница 20: ...spersal Therefore the PV Inverter must have sufficient clearance for the air flow as illustrated below Figure 5 4 2 Required Clearance Space IMPORTANT The NEC requires that the DC disconnect should be mounted between 3 ft 6 5 ft from the ground if the PV Inverter will be used as the standard disconnect ...

Страница 21: ...r orientation for the PV Inverter is very important The PV Inverter should be installed in a vertical position In order to avoid heat dissipating issues ensure there are no any obstacles located or installed near by the PV Inverter Figure 5 4 3 Installing Position and Location ...

Страница 22: ...ay from living or working areas where noise could be a concern E Fix the bracket by using outer mounting holes i A rectangular shaped mounting bracket that shipped with the PV Inverter is able to be used with all types of walls such as stone wall brick wall or wooden wall but it is more important to ensure the wall that is selected will be able handle with the weight of PV Inverter specifically th...

Страница 23: ...oints as appropriate The corner screwing points or the central screwing point as illustrated in the figures below To secure the mounting bracket mark 6 outer holes on the wall drive in the 6 mounting anchors then screw in the 6 M4 screws to each screwing point as illustrated below Figure 5 4 5 Corner screwing fixing mode Figure 5 4 6 Central Point Fixing Mode ...

Страница 24: ...w i Hook up the PV Inverter by aligning the opening of rear side enclosure and place the PV Inverter into each targeted wedge points of the mounting bracket as illustrated below Figure 5 4 7 Install PV Inverter into mounting bracket IMPORTANT Check the mounting bracket again before the PV Inverter is hung on the bracket It is recommended to have least 2 service personnel for this procedure due to ...

Страница 25: ... the exposed electrical components under in moist weather is very dangerous which might cause an electric shock easily In dusty weather electrical components of the wiring box might be damaged if there is heavy dust floating within air during serving period Please be aware and avoid CAUTION It is necessary to disconnect the DC generator and AC Utility if the wiring box is already wired with any DC...

Страница 26: ...Co Ltd iv Unfasten 2 pieces M4 and 4 pieces M5 screws from the top cover of wiring box as illustrated below Figure 5 4 10 Remove the screws of DC AC Wiring Box Screwdriver A M5 hexagon head screwdriver is required for the procedure ...

Страница 27: ... America Co Ltd Page 25 v Remove the top cover of disconnect box and then find the highlighted location from the below figure and then insert 2 M4 size screws Figure 5 4 11 Screwing Location for the Security Screws ...

Страница 28: ... for DC Input side B DC bypass terminal C DC AC Disconnect D 2 fuse holder for AC Output Side Shipped with dummy fuses E RS 485 Interface Card F 8 fuse holders for DC Input Shipped with dummy fuses G DC input terminal H Protection MOV for AC Output side I AC output terminal J AC Utility configuration dip switch K RS232 Interface Port ...

Страница 29: ...DC input bypass terminal block is 38A and the required torque values of the screws is 17 4 lbf in 20 Kgf cm When the PV Inverter is connected to the PV module through an external combiner and external fuses are used the configuration of DC input cable can be connected with the bypass terminal block directly Positive Polarity Position Negative Polarity Position Figure 6 2 1 Connecting DC Cables wit...

Страница 30: ...e specification of external breakers or fuses shall meet the recommended ratings listed in the following table II If there is no external AC breaker or fuse protector installed it is recommended to have AC protection fuses installed to the AC side And the AC fuse that can be selected from the recommended list as below table indicates To ensure the rating of the fuses that are used for the each mod...

Страница 31: ...net cable is inserted in any RJ 45 port the Link LED will light up in yellow color and blink at 2Hz during signal transferring B Power LED indicator It indicates the connectivity of RS 485 card and it will be lit up in green when the inverter is active C Definition of RJ 45 PoE Ports Figure 6 2 3 RJ 45 PoE ports SW1 Terminating Resistor DIP switch SW2 Communication Mode DIP switch Terminating Bloc...

Страница 32: ...sistor SW1 DIP switch Figure 6 2 4 Terminating Mode Press the pin 1 and pin 2 to set the DIP Switch into on mode for card in the terminal inverter farthest from Data Logger or PC For all the others set it to off Here is example for the configuration of 5 PV inverters which pictured in next page PIN NAME Voltage 1 Tx 400mVp p 15Vp p 2 Tx 3 Rx 400mVp p 15Vp p 4 GND 5 GND 6 Rx 400mVp p 15Vp p 7 VCC 1...

Страница 33: ...rid tied PV inverters can be connected with an Ez Logger Lite on the same communication bus line CAUTION Ensure the configuration of the Terminating Resistor is set per section 6 2 An incorrect setting of the DIP Switch will lead to unstable data transferring E Setting DIP switch for Communication Mode SW2 DIP switch Figure 6 2 6 Communication Mode Press the pin 1 and pin 2 of SW2 Dip switch in or...

Страница 34: ... another RS 485 card The cable must be a Straight Through cable as shown in figure 6 2 7 And it is important to ensure the pin position of Ethernet cable is configured by the same way as shown in figure 6 2 8 Connection Type A Connection Type B Figure 6 2 7 Connecting Mode of Ethernet cable Figure 6 2 8 Pin Definition of Ethernet cable ...

Страница 35: ...t recommended However figure 6 2 9 describes an example of a mixed configuration use Figure 6 2 9 Mixed Connecting Mode H Multiple Connections Terminal Block Usage The terminal block that designed for the RS 485 card is used with twisted wire pairs to establish the connection between each PV Inverter as shown in figure 6 2 10 Figure 6 2 10 Twisted Wires Connecting Model ...

Страница 36: ...PC via RS 485 to RS 232 converter When wiring RS 485 card from Inverter to RS 485 to RS 232 Converter connect opposite pins of RS 485 Receive Pin to Transmit Pin and Transmit Pin to Receive Pin See framed area below Figure 6 2 12 Connecting Mode for RS 485 with RS 232 Ethernet Internet Data Logger RS 485 Up to 1200M Up to 1200M Up to 1200M DIP SW ON Inverter to Inverter Correct Pin Configuration R...

Страница 37: ...for the DC side of PV system The PV Inverter is shipped with dummy fuses solid aluminum cylinders in the shape of the proper fuses Since there are four pairs of DC input ports four fuse holders shall be equipped for the four positive polarity ports and others fuse holders are equipped for the four negative polarity ports Therefore there are supports to have eight fuse folders total to the DC side ...

Страница 38: ...an 1 25 times but less than 1 6 times the short circuit current as 1 56 x Isc IN Calculated by Standard Formula A 4 85A x 1 56 7 56A B Implemented the above result within 1 56 x Isc IN C The calculation result will be 7 56A IN That means installer must to select a fuse rating that is greater than 7 56 A but must lesser than 9 70 A Refer to the products information provided from Littelfuse factory ...

Страница 39: ...AC Output Side It is the surge protection that is used to protect the output circuit against excessive voltage of the AC connections I AC Output Terminal Block It is the terminal block that is used to connect AC cables from the utility system also known as the public grid Each model of the Eaton grid tied PV Inverter requires different sizes of AC cables The following table indicated the cable siz...

Страница 40: ...tion dip switch that is embedded within DC AC wiring box This dip switch allows the user to do different configurations of the PV Inverter in order to let it connect to the different public grid tied PV systems using the same inverter The dip switch is located at the right bottom side of wiring box which just under RS 485 interface card and nearby the RS232 interface port as below shown in figure ...

Страница 41: ...2 interface the RS 485 interface card should be disabled manually by switching off the SW2 DIP switch as shown in figure 6 2 15 Therefore it is important to know the status of SW2 DIP switch when service personnel are dealing with the communication interfaces Figure 6 2 15 Enable mode for the RS232 interface Firmware upgrades are also available and can be done via RS 232 interface All PV Inverters...

Страница 42: ...ing the output breaker 6 4 Knockouts for the AC and DC wiring PV Inverters is equipped with different size of knockouts in the wiring box which can be used for the cable configuration of DC side and AC side For the convenience of the installer or system integrator knockouts can be utilized in four different directions and there are two different sizes of the knockouts available to be selected as s...

Страница 43: ...bo 1 1 4 in 1 in 3 Combo 3 4 in 1 2 in 1 Right side Combo 1 1 4 in 1 in 3 Combo 3 4 in 1 2 in 1 Open the knockouts for wiring CPS PV Inverter supports configurations of wiring from different directions with conduits For the knockouts two different sizes can be used and the diameter of these knockouts is shown in figure 6 4 2 Each knockout has two different levels of opening area that can be used i...

Страница 44: ...nts of inner level Figure 6 4 5 Knocking points of outer level Tools A M4 size slotted screwdriver and hammer are required for the opening procedure of knockouts Inner level area Outer level area Upper Knocking Point Lower Knocking Point Right hand side Knocking Point Left hand side Knocking Point 0 5 0 75 1 25 1 ...

Страница 45: ... 4 7 Knocking point of outer level IMPORTANT Be sure to follow all instructions to strike knock out the opening hole by the proper procedures Otherwise the opening area of knockout can be easily damaged if improper tools are used or any improper procedures are done for the opening please beware 1st Step Use tools to target upper strike point and knock it 2nd Step Use tools to target bottom strike ...

Страница 46: ...t connection for the DC side of PV system Figure 7 1 1 Insert a conduit to the wiring box A Before plugging the DC connectors with the cables of PV strings it s important to conduct polarity check by following the steps below i Using multi meter to measure the PV strings cable ends and check the polarity ii The positive terminal of cable should match the Female Connector iii The negative terminal ...

Страница 47: ...e a multi meter to measure the DC input voltage that is generated from the PV modules It must not exceed 600VDC IMPORTANT The CPS grid tied PV Inverter is designed with a transformer less topology It is recommended NOT connecting the Inverter with the PV modules that require positive or negative polarity to ground And it is also necessary to have a circuit breaker or fuse switch installed between ...

Страница 48: ...arity cable in the DC terminal by a screwdriver with the required torque value v Connecting DC negative polarity cable to the DC negative pole terminal in the wiring box vi Tighten the DC negative polarity cable in the DC terminal by a screwdriver with the required torque value vii Double confirm the DC cable from the DC terminal in order to ensure all the DC cables have been tighten firmly in pro...

Страница 49: ...he correct connections of the PV modules according to the electrical specifications IMPORTANT It is important to follow the standard formula for the DC fuse selection if string fuses are planned to be used Insulation Protection An insulation glove should be worn during the service period D When the DC power is delivered from an external combiner to the wiring box of the PV Inverter use a multi met...

Страница 50: ...e L2 location as shown in the above table For 240V split grid system a split phase configuration can be used by 3 AC wires connected to the PCC s L1 L2 and N location and a ground cables connected to the N location as shown in the above table For 277V 3 phase Y grid system a wye type configuration can be used by 2 AC wires connected to L1 and N locations with a ground cables connected to the N loc...

Страница 51: ... the PV Inverter can be used in the different utility grid systems The configuration setting of this dip switch is described in figure 7 2 1 The following tables described the functions that can be enabled through the PIN configuration on the utility configuration dip switch It is recommended that a qualified service personnel complete the configuration of this DIP switch during the installation p...

Страница 52: ...y DIP switch Setting 1 2 3 Pin 1 Pin 2 Pin 3 DIP switch ON OFF OFF 208 Delta Corner grounded L1 L2 G XKW 208 Delta Corner grounded ON OFF ON 240 Delta Corner grounded L1 L2 G XKW 240 Delta Corner grounded ON ON OFF 480 Y 277 V L1 L2 G XKW 277Vac System ON ON ON 240V 120V split phase 240V 120V Stinger L1 L2 N G XKW 240Vac Split ...

Страница 53: ...nd of utility system being used and then select the corresponding setting of utility configuration DIP switch as per the instructions in Table 7 2 1 before the procedures for AC connection C Use a multi meter to measure the AC voltage from the combiner box for AC utility It is important to confirm the configuration of AC utility matches with that of the utility configuration DIP switch D Refer to ...

Страница 54: ...1 Kgf cm Terminal block labeled with G Admissible conductor size 10AWG Torque value 15 6 lbf in 18 Kgf cm 33 1 lbf in 38 1 Kgf cm IMPORTANT The selection for the AC cable size and required torque values for the Position 1 Position 2 Position 3 is referred to the table 310 16 in the National Electrical Code NEC E Connect the AC cables with PV inverter by inserting them through the conduits into wir...

Страница 55: ...e ground symbol pole On the other hand please ensure the setting of the AC DIP switch has been set correctly with the applied grid system Figure 7 2 6 Connect the AC Cables to Correct Positions H Tighten the screws for the AC cables with the required torque values as listed in the Table 7 2 2 Then turn on the circuit breaker from the utility panel or switchboard and use a multi meter to measure wh...

Страница 56: ...Page 54 Copyright CPS America Co Ltd J Lastly reinstall the top cover of wiring box by tightening 2 M4 and 4 M5 screws as shown below Figure 7 2 7 Reinstall the top cover of wiring box ...

Страница 57: ...nu Display date and time of the current day DC Voltage and DC Current Menu Display the DC voltage and DC current from the PV array AC Voltage and AC Current Menu Display the output AC voltage and AC current Frequency and Output Power Display the AC frequency and the instant output power of the unit Nominal Power and Grid System Menu Display the nominal power of the PV Inverter and voltage of the A...

Страница 58: ... Menu It is a menu that will display the output energy for the past 52 weeks E Month Display Menu It is a menu that will display output energy for the past 12 months EXIT Display Menu It is a menu that is used to return back to Etoday menu the level 1 display menu Etoday Energy E Day Date Output Energy E Week EXIT Week Output Energy Month Output Energy Press Enter Press Enter Press Enter Press Ent...

Страница 59: ... and time of the PV Inverter The Enter button is used to change between different units of time and the direction buttons are used to adjust the value of the unit such as year month day hour minute and second IMPORTANT Operational data will be recorded by the date and hour Therefore it is important to ensure the time of inverter is adjusted correctly Date Hour Adjusting Year Press Enter Press Ente...

Страница 60: ... and internal cooling fans are not working properly 2 FAN1 Lock is the second kind of failure message when the external cooling fan is not working properly 3 FAN2 Lock is the third kind of failure message when the internal cooling fan is not worked properly If FAN1 Lock is indicated on the CPS SCE6KTL O US and CPS SCE7KTL O US models please check whether there is any obstacle stopping blocking the...

Страница 61: ...cedures describes how to change the cooling fan please read and understand all procedures before doing so A Switch off the DC AC disconnect switch and wait for at least three minutes to discharge the stored energy in the PV inverter Figure 9 1 1 Turn off DC AC switch B Unfastening all screws located in each corner as highlighted in figure 9 1 2 After the screws are removed take off the top cover o...

Страница 62: ...the cooling fan as shown in Figure 9 1 3 Figure 9 1 3 Disconnect the power cables of the cooling fan D Replace with a new cooling fan by connecting its power cable to PV Inverter Then re tighten the 4 screws at the top cover E Switch on the DC AC disconnect switch to complete the fan replacement procedure ...

Страница 63: ...sary not to remove the top cover of wiring box until 3 minutes after DC AC disconnect switch is turned off It is necessary to turn off the external DC AC breakers if they exist Otherwise it is important to disconnect all the PV modules and AC utility connections before the service of fuse replacement The PV Inverter must be disconnected from all sources of power supply Refer service to only qualif...

Страница 64: ...m the recommended list of brands and rating as described in the DC and AC protection chapters in section 6 2 of this manual Figure 9 3 3 Install a new fuse D Install the fuse cover with the new fuse into the correct fuse holder as shown in figure 9 3 4 It is important to ensure the fuse cover is inserted tightly into fuse holder in order to complete the fuse replacement and re installation procedu...

Страница 65: ...rs 4 4 4 4 Max DC current 19 A 26 A 32 A 37 A Max Input Current per String 20A 20A 20A 20A DC insulation resistance 2 2MΩ DC Disconnection Type Switch Output AC Nominal AC power 240Vac 277Vac 4000W 5000W 6000W 7000W Nominal AC power 208Vac 3800W 4600W 6000W 7000W Max AC power 240Vac 277Vac 4000W 5000W 6000W 7000W Max AC power 208Vac 3800W 4600W 6000W 7000W Grid Connection Type Single phase 240V Sp...

Страница 66: ...A 22 5A 28 5A 33 2A Max AC current 7 277Vac system 16 4A 20 5A 24 6A 28 7A System Topology Transformerless Max Efficiency 97 5 CEC efficiency 97 Stand by Night Consumption 8 7W 0 2W Environment Protection Degree NEMA 3R Cooling Forced air cooling Operating Humidity 0 95 non condensing Operating Altitude 6562ft 2000m without derating Operating temperature range 9 25 50 5 Regulation range 244 305Vac...

Страница 67: ... Display and Communication Display LCD LED Communication RS232 RS485 Mechanical Data Dimensions WxHxD 17 0x33 4x8 4in 434x850x213mm Weight 86lbs 39kg 90lbs 41kg 101lbs 46kg 101lbs 46kg Safety Safety and EMC Standard UL1741 2010 CSA C22 2 No 107 1 01 FCC PART15 Class B Grid Standard IEEE1547 2003 IEEE1547 1 2005 ...

Страница 68: ...voltage is higher than 150V inverter is waiting for feeding to the grid 2 After Startup Input voltage range is at 80 100V Check Grid Checking xxxS When PV voltage 150V inverter is checking grid conditions Feeding Grid Normal Inverter is feeding power to the grid FLASH FLASH FLASH Firmware II Monitoring Parameter Messages Operation Condition Messages Descriptions Instantaneous Output Power Pac xxxx...

Страница 69: ...ncy No Utility No Utility Utility is not available Input Voltage too High PV over voltage Input voltage higher than the 600V Ground I Fault Ground I Fault Leakage current on ground conductor is too high V Inverter Fault Messages Operation Condition Messages Descriptions Consistent Fault Consistent Fault The readings of 2 microprocessors are not consistent It could be caused by CPU and or other cir...

Страница 70: ...tion for System Faults Messages A Isolation Fault Conditions The resistance between the PV or PV and grounding is outside the permissible range 2MΩ Corrective Actions Restart the inverter again If fault still occurs after the unit is restarted contact the system installer immediately Ask the system installer to check if the PV Inverter and PV Modules are properly insulated throughout the solar sys...

Страница 71: ...ity system and the AC connections of the PV Inverter Check the AC fuses of the PV Inverter If failure remains disconnect the PV Inverter and contact the system installer D PV Over Voltage Conditions DC voltage fed by the PV module is higher than permissible range 600Vdc Corrective Actions Disconnected PV modules immediately Check the configuration of the strings for the PV modules and ensure the m...

Страница 72: ...nt cooling fan and remove the obstacle if any If the top fan is not functioning it may be replaced as per the instructions described in section 9 1 If fault remains disconnect the PV Inverter and contact the inverter installer C Over Temperature Conditions The internal temperature is higher than normal value Corrective Actions Disconnect PV Inverter for a period of time 30 minutes and then restart...

Страница 73: ...access problem Corrective Actions Restart the PV Inverter If fault remains disconnect the PV Inverter and contact the inverter installer G SCI failure Conditions Communication between the inside MCU is abnormal Corrective Actions Restart the PV Inverter If fault remains disconnect the PV Inverter and contact the inverter installer H High DC bus Conditions The DC BUS inside is higher than expected ...

Страница 74: ...verter If fault remains contact the inverter installer to check the grounding of the PV Inverter If the fault remains disconnect the PV Inverter and contact the inverter installer J Damp Fail Condition The resistance stick is working outside the permissible range Corrective Actions Restart the PV Inverter If fault remains disconnect the PV Inverter and contact the inverter installer ...

Страница 75: ...ht CPS America Co Ltd Page 73 12 Power Curve Allowable Output Power vs String Voltage as shown below CPS SCE4KTL O US CPS SCE5KTL O US CPS SCE6KTL O US CPS SCE7KTL O US Figure 12 1 1 Line loss vs cable length ...

Страница 76: ...Page 74 Copyright CPS America Co Ltd Appendix Configuration of Wiring Box ...

Страница 77: ...I CHINT POWER SYSTEMS CO LTD Headquarters Building 4 No 855 Wenhe Road Songjiang District Shanghai China Tele 86 21 3779 1222 6300 Fax 86 21 3779 1222 6001 Website www chintpower com na This manual Version 1 0 En 2012 10 is subject to change without prior notification Copyright is reserved Duplication of any part of this issue is prohibited without written permission ...