50
-
6. OPERATION/SETTING
6.7 Alarm Specifications
(1) Alarm Type
The following are the types of alarm and examples of
activation/reset of alarm.
Alarm type
Alarm level
Upper
limit/lower limit
“L” alarm (lower
limit alarm)
“H” alarm (upper
limit alarm)
* Combination of the alarm is described as “Alarm type”. Alarm
type of this product is upper limit/lower limit alarm.
Each alarm status (“L”alarm and “H” alarm) is described as
“Alarm level”.
(2) Alarm Deadband
Alarms are activated when input values become
alarm setting values (lower limit value or less/
upper limit value or more), and they are reset
when input values returns to the values just before
the alarm setting values.
The difference is called “Alarm deadband” which is
indicated with % of scale width (measuring range).
It is set to 0.4% for this product.
Alarm Deadband
Lower limit alarm
Upper limit alarm
MIN MAX
(Reset)
Deadband
(Activation)
ON
OFF
Alarm setting value
MIN MAX
(Reset)
Deadband
(Activation)
ON
OFF
Alarm setting value
Time
Measured value
“
H” alarm setting
value
“
L” alarm activation
“
H” alarm activation
Normal
range
“
L” alarm setting
value
Alarm Deadband
On “L” alarm reset
Deadband
On “H” alarm reset
Deadband
0.4%
0.4%
•
Upper limit/lower limit alarm
1. “L” alarm (lower limit alarm): Alarms are activated on alarm value
≧
measured value.
2. “H” alarm (upper limit alarm): Alarms are activated on alarm value
≦
measured value.
Example of Alarm Activation/Reset
Upper Limit/Lower Limit Alarm
“
H” alarm setting value
Measured value
Time
Normal range
“
L” alarm setting value