15.7 CONTROL OF AUTOMATIC CONDENSATE DRAINAGE FOR DRYER (IF INCLUDED) AND CONDENSATE DRAIN.
BEFORE PERFORMING ANY TYPE OF SERVICING, THE MACHINE MUST BE SHUT DOWN AND ISOLATED FROM THE
MAINS POWER AND COMPRESSED AIR DISTRIBUTION NETWORK.
The proper operation of the automatic condensate drain must be checked by observing the correct outflow of the drained liquid through the
drain pipe Ref. 9 Fig. 20.
Proceed as follows:
- Remove the panel Ref. 8 Fig.20
-
Press the “TEST” button Ref. 1 Fig. 20 for a few seconds and check that the condensate is properly drained through the drain
pipe Ref.9
Fig. 20.
- Remount the panel Ref. 8 Fig.20
“Green LED”
: Condensate drain working properly (Automatic, Manual Drainage, Self-cleaning).
“Blue LED”
: Condensate drain in “Timer Drain” mode
Request for drain Service (See Chap.15.8).
If normal drain operation is not restored after the drain service (GREEN LED), contact the customer centre.
15.8 DRAIN SERVICE
IMPURITY FILTER CLEANING FOR DRYER (IF INCLUDED)
Proceed as follows:
- Shut down the machine using the button Ref. 4 Fig. 20: in this way, the machine will stop after the unloading run time.
- Close the tap Ref. 5 Fig. 20 (machine with / without tank).
- Remove the panel Ref. 8 Fig. 20
-
Depressurise the dryer by pressing the “TEST” button of the automatic condensate drain (for about 10
-20 seconds) Ref.1 Fig.20
(machine without tank).
- Open the power disconnect switch Ref. 2 (compressor) and Ref. 3 (for dryer) Fig. 20.
- Depressurise the dryer and tank, opening the condensate drain tap Ref. 10 Fig. 20 (machine with tank).
- Remove the drain cap Ref. 6 Fig. 20
- Remove the impurity filter Ref. 7 Fig. 20
- Clean the filter with a blast of air from the inside out
- Remount the filter, screw in the cap Ref. 6 Fig. 20
- Remount the panel Ref. 8 Fig. 20
- Close the tap Ref. 10 Fig. 20.
FIG. 20
1
7
6
3
5
8
4
9
2
5
10