If the INVERTER ALARM RESET is unsuccessful:
- Disconnect the power supply to the machine for
15min.
- After having restored the power supply,
RESET
the
Control Board
.
If the problem persists,
contact the technical service centre
Inverter warnings and alarms
Error
number
Alarm cod. on
GRAPHIC control
board
Error text
Warning
Alarm
Trip
locked
Cause of problem
2
Error live zero
X
X
The signal on terminal 53 is too low (normal when a
machine with STD+ controller is started).
4
16384
Phase loss
on supply line
X
X
X
Missing phase on supply line or voltage imbalance too
high. Check power supply.
7
2048
DC overvoltage
X
X
The intermediate circuit voltage is over the limit (check
supply).
8
1024
DC undervoltage
X
X
The intermediate circuit voltage is below the “low
voltage warning” limit (check supply).
9
512
Inverter overload
X
X
Load greater than 100% for too long. Check the
compressor mechanics and loading/unloading valve.
10
256
High motor ETR
temperature
X
X
The motor is too hot due to the load being greater than
100% for too long. Request assistance from the
distributor.
11
128
Motor thermistor
disconnected
X
X
The thermistor or thermistor connection are
disconnected (if thermistors are included). Request
assistance from the distributor.
13
32
Overcurrent
X
X
X
The maximum inverter current limit has been
exceeded. Request assistance from the distributor.
14
4
Ground fault
X
X
Discharge from output phases to ground.
16
4096
Short circuit
X
X
Short circuit in motor or on motor terminals.
17
16
No communication
(RS 485 port)
X
X
Connection cable or settings
24
Fan malfunction
X
X
Fan malfunction
30
U phase loss
X
X
U phase of motor does not exist. Check phase.
31
V phase loss
X
X
V phase of motor does not exist. Check phase.
32
W phase loss
X
X
W phase of motor does not exist. Check phase.
36
Voltage drop
X
X
Problem with supply.
38
Internal fault
X
X
Compressor contact service.
44
Ground fault
X
X
Discharge from output phases to ground. Request
assistance from the distributor.
47
Control voltage fault
X
X
X
Possible overload of 24V DC supply.
48
VDD1 supply low
X
X
Low control voltage. Compressor contact service.
50÷58
Configuration error
X
Request assistance from the distributor.
59
Current limit
X
The current is higher than the current limit value.
Request assistance from the distributor.
60
External interlock
X
The external interlock has been activated.
Reset on the compressor control board. If the alarm
doesn’t reset, request assistance from the distributor.
66
Low heat sink
temperature
X
This warning is sent by the temperature sensor in the
IGBT module.
69
Power board
temperature
X
X
X
The power board temperature sensor is too hot or too
cold.
79
Incorrect
configuration of
power section
X
X
Internal fault. Request assistance from the distributor.
80
Drive initialised
X
All the parameter settings are initialised as settings in
the default values of the Inverter. Request assistance
from the distributor.
84
Internal error
X
X
Request assistance from the distributor.
85
Button disabled
X
Drive settings.
86
LCP inverter display
copy failed
X
Parameters incompatible or firmware version not
correct.
87
Auto DC braking
X
Inverter internal limiting.
88
LCP inverter display
data incompatible
X
89
Read-only
parameter (not
editable)
X
90
Internal error
X
X
Attempt to update the same parameter simultaneously.
94
Internal error
X
X
Request assistance from the distributor.